Springs can be ordered from Oilon Webshop.
Setting pressure regulator at minimum load
1. Start burner at minimum load. At minimum load throttle valve setting is 5°-10°.
2. Adjust combustion to safe level using flue gas analysis. Measure pressure regulator
outlet pressure from gas valve measuring point.
3. Turn adjustment spindle clockwise until gas amount corresponds with required
burner minimum load. Check combustion using flue gas analysis, when raising
pressure. Adjust burner if necessary.
Check gas valve measuring point position from the gas valve
manufacturer manual.
Adjust the pressure regulator outlet pressure to its final level with the
burner running at full load.
To adjust outlet pressure
219598a ver. 1
1. Unscrew protective cap
A
.
2. Use a chisel-point screwdriver. to adjust spindle
B
:
a. Turn the spindle B clockwise. This increases the outlet pressure.
b. Turn the spindle B counterclockwise. This reduces the outlet pressure.
3. Check the setpoint.
4. Screw on the protective cap
A
.
38 (102)
M4263 2206EN