background image

 

 

 

 

 

 

RE010070948EN  

18/23 

4.2. Troubleshooting 

Error message codes  

No. 

Definition 

Sensor 

Cause 

Action 

10 

Outside sensor

 

B9 No 

outside 

sensor. 

Check outside sensor 
connection. 

30 

Flow sensor 1

 

B1 No 

measurement 

from outgoing 
water 

Check L1 flow sensor 
connection. 

32 

Flow sensor 2

 

B12 No 

measurement 

from outgoing 
water 

Check L2 flow sensor 
connection, additional. 
 

33 

Flow sensor HP

 

B21 No 

measurement 

from outgoing 
water 

Check HP sensor 
connection. 

35 

Source inlet sensor

 

B91 No 

measurement 

from source inlet 
sensor 

Check source inlet 
sensor. 

36 

Hot-gas sensor 

B81 No 

measurement 

from hot gas 
sensor 

Check hot gas sensor 
measurement connection. 

40 

Condenser difference 
max.limit

 

 Too 

high 

temperature over 
condenser 

Check heating circuit 
venting, increase pump 
rotation speed. 

41 

Condenser difference 
min.limit 

 Too 

high 

temperature over 
condenser 

Slow down pump rotation 
speed. 

42 

Evaporator difference 
max. limit 

 Too 

large 

temperature 
difference over 
evaporator 

Check ground circuit 
venting, increase pump 
rotation speed. 

43 

Evaporator difference 
min. limit 

 Too 

small 

temperature 
difference over 
evaporator 

Check compressor 
operation. 

106 

Source temp too low

 

 

Too low ground 
circuit 
temperature 

Vent ground circuit, check 
that pump rotation speed 
is at maximum. 

107 

Hot-gas compressor 1

 

 Compressor 

hot 

gas temperature 
too high 

Adjust maximum 
temperature for outgoing 
water lower.  

222 

High-press in HP 
operation

 

E10 Compressor 

has 

reached 
maximum 
pressure at 
pressure side 

Adjust maximum 
temperature for outgoing 
water lower 

223 

Hi-press on start HC

 

E10 Compressor 

has 

reached 
overpressure at 
HC circuit start-
up 

Check that condenser 
pump is operational, and 
fuse is not blown out. 

224 

Hi-press on start DHW

 

E10 Compressor 

has 

reached 
overpressure  at 
DHW heating 
start-up. 

 

Содержание Geopro RE

Страница 1: ...RE010070948EN Operation manual Geopro RE Read these instructions carefully...

Страница 2: ......

Страница 3: ...e settings 9 3 3 3 Language settings 9 3 3 4 Changing room temperature settings 10 3 3 5 Changing heating circuit operating mode 10 3 3 6 Changing heating curve 10 3 3 7 Setting holiday heating circui...

Страница 4: ...sing the device Given instructions must be followed Throughout this manual the following three symbols are used to point out very important information WARNING A warning alerts you to possible danger...

Страница 5: ...condensator and energy is saved at required heating level Then condensated refrigerant pressure is reduced into compressor suction pressure level at expansion valve causing part of the refrigerant to...

Страница 6: ...er tank or loop in separate domestic hot water buffer tank 2 2 Collecting heat RE ground source heat pump s heat source is usually a drilled well The number and depth of wells depend on heating demand...

Страница 7: ...supply water temperature 2 4 Sizing heat pump Heat pump can be sized up to operate at partial or full capacity With partial capacity heat pump maximum capacity is sized up to correspond 60 80 of buil...

Страница 8: ...button not in use Automatic According to programmed time Comfort setpoint Reduced setpoint Frost protection setpoint 3 Info button displays measurement results and failures 4 Back button quit adjusti...

Страница 9: ...Change user level from basic menu display 2 Press OK button 3 For user level list press Info button for 3 seconds 4 Select user level by turning adjusting wheel and confirm selection by pressing OK bu...

Страница 10: ...setpoint Frost protection If selected operating mode is automatic set corresponding time program with desired time periods Set time periods at Time program heating circuit 1 2 menu First select dates...

Страница 11: ...ot water nominal setting at this menu at other times setting is Reduced setpoint 3 3 9 Domestic hot water forced charge If domestic hot water consumption increases momentarily perform forced charging...

Страница 12: ...program time program 5 With setting 24 h day cooling is continuously on With heating circuit time program cooling circuit operates according to heating circuit 1 Time program 5 can be set as other ti...

Страница 13: ...ff Clock time when temperature level is lowered to reduced setpoint 505 3rd phase on Clock time when temperature level is raised to comfort setpoint 506 3rd phase off Clock time when temperature level...

Страница 14: ...641 Preselection Select phase number 8 different time period options Phase 1 642 Start Date when setpoint will be reduced 643 End Date when values is reset 648 User level Defines reduction level for t...

Страница 15: ...ted Operational only in automatic mode 18 Domestic hot water Line Parameter Function Arvo 1610 Nominal setpoint Domestic hot water nominal setpoint temperature 60 1612 Reduced setpoint Domestic hot wa...

Страница 16: ...model 2 Room temperature for circuit 2 outside sensor if any 8771 Room temp model 2 Heating circuit 2 room setting 8773 Flow temp 2 Heating circuit 2 outgoing water temperature 8774 Flow temp 2 Heati...

Страница 17: ...Open screen carefully there is fluid in pipe Note Check that you have necessary tools available 1 Switch off device from main switch 2 Close screen isolation valves 3 Open cover 4 Detach screen and r...

Страница 18: ...r difference min limit Too high temperature over condenser Slow down pump rotation speed 42 Evaporator difference max limit Too large temperature difference over evaporator Check ground circuit ventin...

Страница 19: ...erloaded E11 Compressor overloaded 324 BX same sensors BX outputs connected using same address 325 BX e module same sens BX outputs connected using same address 327 E module same funct Same function f...

Страница 20: ...GSSH010020904FI_draft 4 23...

Страница 21: ......

Страница 22: ...OILON HOME OY P O Box 5 15801 Lahti Visiting address Tarmontie 4 15860 Hollola Tel 03 85 761 fax 03 857 6239 info oilon com www oilon com...

Отзывы: