Time prog
4 DHW
Line
Parameter
Function
Setting
600
Preselection
Select dates for time limits.
Mon - Sun
601
1. Phase on
Clock time when temperature level is raised to comfort
setpoint.
04:00
602
1. Phase off
Clock time when temperature level is lowered to reduced
setpoint.
09:00
603
2. Phase on
Clock time when temperature level is raised to comfort
setpoint.
16:00
604
2. Phase off
Clock time when temperature level is lowered to reduced
setpoint.
22:00
605
3. Phase on
Clock time when temperature level is raised to comfort
setpoint.
---
606
3. Phase off
Clock time when temperature level is lowered to reduced
setpoint.
---
616
Default values
”Yes” resets defaults values.
No
Holiday heating circuit
1
Line
Parameter
Function
Setting
641
Preselection
Select phase number, 8 different time period options.
Phase 1
642
Start
Date when setpoint will be reduced.
---
643
End
Date when values is reset.
---
648
User level
Defines reduction level for temperature.
Reduced
Holiday heating circuit
2
Line
Parameter
Function
Setting
651
Preselection
Select phase number, 8 different time period options.
Phase 1
652
Start
Date when setpoint will be reduced.
---
653
End
Date when values is reset.
---
658
Operating level
Defines reduction level for temperature.
Reduced
Heating circuit
1
Line
Parameter
Function
Setting
710
Comfort
setpoint
Set room temperature for heating circuit to reach at comfort
setpoint.
20
712
Reduced
setpoint
Set room temperature for heating circuit to reach at reduced
setpoint.
18
720
Heating curve
slope
See curves at Changing heating curve.
0,8
730
Summer/winter
heating limit
Temperature when heating circulation is stopped or started.
Operational only in automatic mode.
18