Valve and actuator Installation
Below is a general description of how to install an Esbe VRG130 series control valve
and the associated Esbe ARA600 series actuator. Other valves are installed in a similar
way. For more detailed instructions, please refer to the guide delivered with the valve
and actuator.
Align the bevel on the
valve stem with the slot
on the actuator shaft.
Turn the valve stem to a position corresponding to the piping connection.
● Pay attention to the flow directions and the markings on the valve (triangle,
circle and square).
Install the scale plate at this stage as well.
● Note that when installing the actuator, the actuator control knob must be in
the middle position.
ESBE valve stem ver. 2
A
B
The installation guide delivered with the valve includes other connection options.
Enabling the control valve
Enable the valve from
Initial setup
settings (see chapter
Commissioning
) or from
Heating
settings (see the table below). Enable the valve by selecting
Valve control
as
the setting for the circuit.
DEVICE SETTINGS → SERVICE → HEATING
Heating circuit 1
No
The circuit is not in use.
Direct connection
The heat pump is connected directly to the building’s heating system. The system
has no circulation pump or control valve that would be controlled by the heat pump.
Direct connection, with pump
The system has a circulation pump which is controlled by the heat pump.
Circuit in use
3-way valve
The system has a circulation pump and a 3-way control valve, both of which are
controlled by the heat pump.