Installation & Operation Manual                                                                                               Merlin 1000V 

 

 

 

 Rev: 02    05-22

 

6

 

 

BMS Output 

 

Connections are available on the board for Building Management Systems.  
[NO Normally Open] [COM Common] [NC Normally Closed] 
 
These are volt free connections. 
 
This is a relay that changes state when the gas is on/off and can be used in conjunction with the 12V DC 

output and other external relays that affect other devices and controls such as purge fans and audible 
alarms etc. 

 

Pressure Sensor 

 

Pressure sensors should be screwed to the downstream port of the valve.

 

 

Pressure Sensors are tested and certified to AS 4628/2005.

 

 

The pressure sensor is wired to the [PRESSURE SENSOR] connector and screwed into the downstream 
port of the gas solenoid valve. 

Connect the pressure sensor as shown:  

 
 
The sensor will monitor the gas supply pressure and if pressure drops below 0.5 or 1.2Kpa 

 

the gas valve will close.  
 
See section; Switch Settings - for Pressure options 

 

EM Remote 

 
Connections for remote emergency shut-off or stop buttons is detailed on the circuit board as [EM 

REMOTE]. This is linked out as a factory setting.  

 

Gas Detector / CO2 Monitor 

 

Refer to your gas detector and CO2 monitor manual for further information! 

 

CO2 Monitors are powered via an external supply! 

 
If no detector is being used leave the factory fitted link in.  
A wiring example for a gas detector is shown. 
 
Refer to your gas detector manual for further information. 

 

CO

2

 Monitor. 

To connect a CO2 monitor and gas detector 

 wire in series and power the CO2 

monitor via external mains power supply.  

 
 

 

Содержание Merlin 1000V

Страница 1: ...on Controller with Ventilation Interlocking Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the informati...

Страница 2: ...r CO2 Monitor 6 Fan Switches 7 PD Switches Current Monitors 7 12 VDC 7 Switch Settings Auto RST Panel Auto Reset 7 Switch Settings Pressure Gas Pressure Threshold Configuration 7 Switch Settings EM SE...

Страница 3: ...nty extends to the original consumer purchaser of the product only Warranty disclaimers Any implied warranties arising out of this sale including but not limited to the implied warranties of descripti...

Страница 4: ...hut off the gas solenoid valve at the end of a specific time this time can be adjusted to 2 5 8 hours or can be overridden if required Mounting Cabling If mounting direct to wall ensure the wall surfa...

Страница 5: ...LINE IN terminal and fused at 3A On connecting the mains supply to the panel the red power LED indicator will light up this is located on the front cover OGS Logo Wiring Gas Solenoid Valve Pressure s...

Страница 6: ...rewed into the downstream port of the gas solenoid valve Connect the pressure sensor as shown The sensor will monitor the gas supply pressure and if pressure drops below 0 5 or 1 2Kpa the gas valve wi...

Страница 7: ...g There is a switch located on the circuit board labelled AUTO RST OFF When power is restored after the power cut loss the panel must be restarted manually Default ON This will instruct the system to...

Страница 8: ...meout Period Upon timeout the gas supply will be turned off There are two dipswitches Time 1 Time 2 The system has an auto shut down feature after a selected time These can be configured to select the...

Страница 9: ...NOT operate any appliances Test Fail Under normal working conditions this LED is off When the panel detects a gas leak on start up the LED will illuminate AMBER Gas valve will remain closed OFF OK ON...

Страница 10: ...e chlorine hydrogen chloride alkali metals basic or acidic compounds silicones tetraethyl lead halogens and halogenated compounds Keep your panel in good working order follow these basic principles R...

Страница 11: ...Overvoltage Category II Pollution Degree 2 Equipment Class 2 Environmental Ingress Protection Not Formally Evaluated Operating 10 50 C 14 122 F 30 80 RH non condensing Storage 25 50 C 13 122F up to 9...

Страница 12: ...ensure the equipment performs as intended and is free from any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however OGS can assume no r...

Отзывы: