Installation & Operation Manual                                                                                               Merlin 1000V 

 

 

 

 Rev: 02    05-22

 

9

 

 

Operation 

Initial Power Up 

On connecting mains power, an LED on the front of the panel (OGS Logo) will illuminate red.  

1.

 

Turn the key switch to on position.  

2.

 

Testing LED will illuminate whilst the system checks for gas line. 

3.

 

Gas-On LED should illuminate if gas proving is successful. 

Turn the key switch to the off position to turn the panel off. 
 

Emergency Shutoff Push Button 

The emergency shut off button is located on the front of the panel. There is also a facility for remote shut 

off buttons to be wired in series on the circuit board. The emergency shut off button(s) will cut off the 
gas supply when activated. To reinstate the system, the emergency shut off button(s) will need to be 
reset and the panel restarted.  
 

LED Indicators 

 

 

Gas On

 

When the key switch is turned on, the system will check the installation for gas leaks.  
If gas proving is successful, the LED will illuminate.

 

ON = Gas On / OFF = Gas Off

 

 

 

Testing  

This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the integrity of 
the gas installation upon start up. 

ON = proving the gas line, do NOT operate any appliances.

 

 

 

 

Test Fail  

Under normal working conditions this LED is off. When the panel detects a gas leak on start-up, the LED 
will illuminate AMBER. Gas valve will remain closed. 

OFF = OK / ON = gas proving failed.

 

 

 

Pressure Low  

Under normal working conditions the LED is off. The LED will illuminate AMBER when pressure of the 
gas supply drops below 1.2kPa for 10 secs. The gas valve will close. 

OFF = OK / ON = gas supply pressure low.

  

 

 

 

 

Timeout 

Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down 
has occurred. 

OFF = OK / ON = Auto-shut down activated

 

 

 

EM Stop  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate 
AMBER and the gas will be turned off. The emergency shutoff button must be reset before restarting the 
system. 

OFF = OK / ON = Emergency Shut-Off button activated.

 

 

 

CO2/ Gas Detected  

Under normal working conditions this LED is off. If the external Merlin detector connected detects gas 
this will show RED, and the gas valve will turn off. 

OFF = OK / ON = Gas detected.

  

 

 

Fan Fault 

Under normal working conditions this LED is off. If a fan fault is identified for longer than 10 seconds the 

LED will show RED, and the Gas valve will turn off. Fan fault will only identify when the gas is on only. 

OFF = OK / ON = Gas supply has been shut off due to a ventilation fault. 

 
 

Содержание Merlin 1000V

Страница 1: ...on Controller with Ventilation Interlocking Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the informati...

Страница 2: ...r CO2 Monitor 6 Fan Switches 7 PD Switches Current Monitors 7 12 VDC 7 Switch Settings Auto RST Panel Auto Reset 7 Switch Settings Pressure Gas Pressure Threshold Configuration 7 Switch Settings EM SE...

Страница 3: ...nty extends to the original consumer purchaser of the product only Warranty disclaimers Any implied warranties arising out of this sale including but not limited to the implied warranties of descripti...

Страница 4: ...hut off the gas solenoid valve at the end of a specific time this time can be adjusted to 2 5 8 hours or can be overridden if required Mounting Cabling If mounting direct to wall ensure the wall surfa...

Страница 5: ...LINE IN terminal and fused at 3A On connecting the mains supply to the panel the red power LED indicator will light up this is located on the front cover OGS Logo Wiring Gas Solenoid Valve Pressure s...

Страница 6: ...rewed into the downstream port of the gas solenoid valve Connect the pressure sensor as shown The sensor will monitor the gas supply pressure and if pressure drops below 0 5 or 1 2Kpa the gas valve wi...

Страница 7: ...g There is a switch located on the circuit board labelled AUTO RST OFF When power is restored after the power cut loss the panel must be restarted manually Default ON This will instruct the system to...

Страница 8: ...meout Period Upon timeout the gas supply will be turned off There are two dipswitches Time 1 Time 2 The system has an auto shut down feature after a selected time These can be configured to select the...

Страница 9: ...NOT operate any appliances Test Fail Under normal working conditions this LED is off When the panel detects a gas leak on start up the LED will illuminate AMBER Gas valve will remain closed OFF OK ON...

Страница 10: ...e chlorine hydrogen chloride alkali metals basic or acidic compounds silicones tetraethyl lead halogens and halogenated compounds Keep your panel in good working order follow these basic principles R...

Страница 11: ...Overvoltage Category II Pollution Degree 2 Equipment Class 2 Environmental Ingress Protection Not Formally Evaluated Operating 10 50 C 14 122 F 30 80 RH non condensing Storage 25 50 C 13 122F up to 9...

Страница 12: ...ensure the equipment performs as intended and is free from any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however OGS can assume no r...

Отзывы: