50
Service setting manual
ENG
PARAMETERS FOR FLOOR DRYING
Group F1 contains the parameters for the setting of floor drying.
Table with descriptions of parameters:
Param-
eter
Parameter name
Setting range
Default
setting
F1.1
FLOOR DRYING
0- NO
1- CIRCUIT 1
2- CIRCUIT 2
3- CIRCUIT 1 & 2
0
F1.2
INTERVAL 1: DURATION
1 ÷ 15 days
10
F1.3
INTERVAL 1: START TEMPERATURE
10 ÷ 60 °C
20
F1.4
INTERVAL 1: END TEMPERATURE
10 ÷ 60 °C
20
F1.5
INTERVAL 2: DURATION
1 ÷ 15 days
5
F1.6
INTERVAL 2: START TEMPERATURE
10 ÷ 60 °C
20
F1.7
INTERVAL 2: END TEMPERATURE
10 ÷ 60 °C
50
F1.8
INTERVAL 3: DURATION
1 ÷ 15 days
10
F1.9
INTERVAL 3: START TEMPERATURE
10 ÷ 60 °C
50
F1.10
INTERVAL 3: END TEMPERATURE
10 ÷ 60 °C
50
F1.11
INTERVAL 4: DURATION
1 ÷ 15 days
5
F1.12
INTERVAL 4: START TEMPERATURE
10 ÷ 60 °C
50
F1.13
INTERVAL 4: END TEMPERATURE
10 ÷ 60 °C
20
The procedure for F parameters setting is the same as the procedure for
service settings (see 38).
Param-
eter
Parameter name
Parameter description
Setting range Default
setting
S6.13
LOCATION OF COLD
SENSOR FOR DIFF.
THERMOSTAT
Cold sensor (T8) place of mount, if it is being used for
differential thermostat. In exact we define storage device
which is being warmed with solar collectors or solid fuel
boiler.
1- D. H. W.
TANK
2- HEAT AC-
CUMULATOR
1
S6.14
HEAT PUMP OPERATION
MODE
Setting if heat pump should operate in ON/OFF or
weather compenstaed mode.
1- ON/OFF
2- WEATHER
COMPEN-
SATED
2
S6.15
MAX. HEAT PUMP OUT-
PUT TEMPERATURE
Setting of max. heat pump output temperature when
operating in weather compenstaed mode.
40 ÷ 70 °C
50
S6.16
HEAT PUMP HYSTERESIS Setting of hysteresis for heat pump operation.
2 ÷ 10 °C
4
S6.17
MIN. OUTDOOR TEMP.
FOR HEAT PUMP OPERA-
TION
Setting of min. outdoor temperature below which the heat
pump should switch off.
-30 ÷ 10 °C
11- NO LIMITA-
TION
-10