34
Service setting manual
ENG
General settings:
Para-
meter
Parameter name
Parameter description
Setting range Default
setting
P1.1
AUT. SWITCHOVER
SUMMER / WINTER
Automatic switch-off and switch-on of heating in
respect to average one-day outdoor temperature.
0- NO
1- YES
1
P1.2
AVERAGE OUTDOOR
TEMP. FOR SUMMER /
WINTER SWITCHOVER
Setting of average one-day outdoor temperature at
which the heating should switch-off or switch-on.
10 ÷ 30 °C
18
P1.3
OUTDOOR TEMP. FOR
ACTIVATION OF FROST
PROTECTION
Setting of outdoor temperature by which the frost
protection will activate and run boiler at minimum
temperature.
-30 ÷ 10 °C
-10
P1.4
REQUESTED ROOM
TEMP. WHEN HEATING
IS SWITCHED OFF
Setting of requested room temperature when heating
is switched off.
2 ÷ 12 °C
6
P1.5
TEMPERATURE ROUND
UP
Precision of displayed temperatures.
0- 0.1 °C
1- 0.2 °C
2- 0.5 °C
3- 1 °C
2
P1.6
AUT. SHIFT OF CLOCK
TO SUMMER / WINTER
TIME
With the help of a calendar, the controller carries out
the automatic clock changeover between summer and
winter time.
0- NO
1- YES
1
P1.7
PERIOD OF TEMPERAT.
LOGGING
By setting this field you define how often the meas
-
ured temperatures are saved.
1 ÷ 30 min
5
P1.8
TONES
By setting this field you define whether key pressing is
accompanied with sound signals or not.
0- OFF
1- KEYPAD
2- ERRORS
3- KEYPAD &
ERRORS
1
P1.9
ADVANCED DISPLAY
OF TEMPERATURES
Advanced display of temperatures displays tem-
peratures on main screen in double rows. First row
is measured temperature; second row is required or
calculated temperature.
0- NO
1- YES
1
Settings for the first heating circuit:
Para-
meter
Parameter name
Parameter description
Setting range Default
setting
P2.1
HEAT CURVE STEEP-
NESS
Heating curve steepness indicates what temperature
is required for the heating bodies by a determined
outdoor temperature.
See chapter Heating curve.
0,2 ÷ 2,2
0,7 - floor
1,0 - ra-
diators
P2.2
PARALLEL SHIFT OF
HEATING CURVE
Setting of parallel shift of heating curve or calculated
stand-pipe temperature.
Use this setting to eliminate deviation between actual
and required room temperature.
-15 ÷ 15 °C
0
P2.3
DURATION OF BOOST
HEATING
Duration of boosted room temperature by changeover
from night to day heating period.
0 ÷ 200 min
0
P2.4
ROOM TEMPERATURE
INCREASE BY BOOST
HEATING
Boost room temperature increase by changeover from
night to day heating period.
0 ÷ 8 °C
3