Operating manual
DKS - classic DKS - expert
33
5.7
11th level - Parameters of heat generator
6
Assistance for start-up and elimination of errors
6.1
Checking the controller
1. Open the cover
2. Press the RESET key
The controller is now initialised. The following sequence is then observed on the
display:
3. The software number (e.g., 521822) appears
4. This is followed by the software release (e.g., SW 6.3)
5. Then all the segments are displayed briefly
If the controller display then reverts to normal, the internal function test was
successful.
Parameter
Function
Setting
range
Factory
setting
Basic setting
Date:
Adaptions
Date:
Un
ity
classic
expert
1(green) 2 (red) 1(green) 2 (red)
X = active
11-4
Cancel operating data
on÷off
off
-
X
X
Operating data can be reset to "0".
off = standard
on = reset of operating dates to "0".
Note: After having set "on", programming level has to be changed or the cover to be closed. About 30 seconds later
setting returns automatically to "off".
11-5
Gen. Power controller
on÷off
off
-
X
X
on = 2 stage burner
off = 1 stage burner