Operating manual
DKS - classic DKS - expert
22
4.1.2
Room-temperature compensation
(Reinforcement room influence, p-part) (parameter 3-7)
If the measured room-temperature deviates from the set value (e.g. on account of
extraneous sources of heat, such as sunlight) the controller corrects the flow tem-
perature in accordance with the value set for parameter 3-7. This value indicates
the number of °C by which the flow temperature is raised or lowered for each °C
of the room-temperature deviation.
• Actual room temperature higher than set value: decrease in flow temperature
• Actual room temperature lower than set value: increase in flow temperature
Recommended settings:
The setting has the following effect:
Radiator heating
room/outside temperature
depending
weak compensation
1-3
middle compensation
4-6
strong compensation
7-10
underfloor heating
1-4
no compensation
0
Adjusted room temperature
set value
Δ
TV
Change of flow temperature
Δ
TI
Room temperature deviation
TV
soll
from the controller in accor-
dance with the heating curve
counted flow temperature set
value
set value
-
4
+4
3
6
9
- 3
-2
-1
+1
+
2
+3
0
soll
soll
Change of flo
w t
emper
atur
e [K]
Room temperature deviation [K]