Operating manual
DKS - classic DKS - expert
28
5
Overview of settings
5.1
3rd level
Parameter
Function
Setting range
Factory setting
Basic setting
Date:
Heating circuit
Adaptions
Date:
Heating circuit
Un
ity
classic
expert
1(green) 2 (red) 1(green) 2 (red)
X =active
3-0
Room protection temperature
3 ÷15
10
°C
X
X
It is valid for all heating modes if changed to holyday, standby, summer. With room temperature sensor (remote con-
trol FS 5601) room temperature becomes reference temperature.
3-1
Fix point temperature
10÷80 25
°C
X
X
Flow temperature at 20 °C outside temperature valid for all slopes.
Recommended values (basic values):
Floor heating system = 25 °C;
Radiator heating system = 35 °C
3-2
Heating limit with reduced
operating
(automatic programs only)
-10 ÷20 5
°C
X
X
With average outside temperature above set value = heating gets turned off.
With average outside temperature below set value - 2 K = heating gets turned on.
If the set value is below 2 °C frost protection mode becomes active.
3-6
Start optimisation
0÷999
0
m
X
X
The set time refers to -10 °C outside temperature.
It results the following anticipation:
•
With outside temperature at -10 °C: 100 % of the set value
•
With outside temperature at 20 °C: 0 % of the set value
Recommended settings for basic value:
•
Floor heating system = 210 (minutes)
•
Radiator heating system = 150 (minutes)
•
Disabled, no function = 0
3-7
Room temperature compensa-
tion
(With remote control FS 5601 only)
0÷10
0
K/K
X
X
•
Room temperature to high in the room = decrease of flow temperature
•
Room temperature to low in the room = increase of flow temperature
0 = no compensation
1-3 = weak compensation
4-6 = average compensation
7-10 = strong compensation
Note: With floor heating systems do not exceed setting 4.