68
Swimming pool heat pump
List of default settings
4.10
* Setting 2 is for modifying the temperature deviation in relation to the required
temperature, causing the heat pump to restart.
Example: If the value of setting 2 is +3 °C, the heat pump will restart after the required
temperature (e.g. +27 °C) has been reached as soon as the pool temperature drops down
to +24 °C (27 – 3).
** Setting 3 is for modifying the exact temperature for heat pump shutdown.
Example: By configuring the compressor shutdown at +2 °C and the required tempera-
ture at +27 °C, the heat pump will stop working automatically as soon as the pool tem-
perature r29 °C (27 + 2).
No.
Description
Adjustment range Default setting
Remark
0
1
2*
3**
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Automatic restart
0 = Off
1 = On
1
adjustable
Programming Start/Stop times
0 = once
1 = daily
1
adjustable
Adjustment of temperature difference for
restart
adjustable from
+2 up to +10 °C
+3 °C
adjustable
Adjustment of compressor shutdown margin
adjustable from
0 up to +3°C
0 °C
adjustable
Auto-activation time before de-icing
commences
adjustable from
30 to 90 min.
40 min.
adjustable
De-icing activation temperature
adjustable from
0 to -30°C
-7 °C
adjustable
De-icing deactivation temperature
adjustable from
+2 up to +30 °C
+20 °C
adjustable
Max. de-icing duration
adjustable from
0 to 15 min.
8 min.
adjustable
Maximum temperature
+25 up to +40 °C +40 °C
adjustable
Pump stopping time when temperature is
reached (if setting 10 = 1)
adjustable from
3 to 20 min.
15 min.
adjustable
Reserved – do not modify
0 / 1
1
adjustable
Water intake temperature
-9 up to +99 °C
actual data
Water outlet temperature
-9 up to +99 °C
actual data
Coil temperature
-9 up to +99 °C
actual data
Air outlet temperature
-9 up to +99 °C
actual data
Ambient air temperature
-9 up to +99 °C
actual data
Setting for selecting pump operating mode
0 = only cooling
1= c
heating
2 = only heating
1
adjustable
Filtration pump servo-control mode
0 = normal/
1= special
1
adjustable (see
section 5.2)
Compressor thermal protection
adjustable from
+95 up to +120 °C
95-96-97-98-99-A0-
A1-A2-A3-A4-A5-
A6-A7-A8-A9-b0-b1-
b2-b3-b4-b5-b6-b7-
b8-b9-C0
+118 °C
displayed values
b8
adjustable
GB