16.5
Error table
Code
Malfunc-
tion store
code
Error description
Possible cause/ remedy
115
Er 01: Hot water sensor
defect
Replace sensor
116
Er 10: Outside sensor de-
fect
Replace sensor
117
Er 14: Mixer sensor defect Replace sensor
124
Er 20: TWR sensor defect Replace sensor
120
Er 22: Switch-off sensor
TPM or TWR defect
Replace sensor
136
Er 23: TPV sensor defect
Replace sensor
118
Er 24: Buffer sensor defect Replace sensor
114
Er 29: TWV sensor defect Replace sensor
11
11
Er 30: Phase monitor
Check power supply
134
Er 32: THG sensor defect
Replace sensor
138
Er 33: High pressure sensor
defect
Check sensor
137
Er 34: Low pressure sensor
defect
Check sensor
5
5
Er 36: High pressure
Insufficient heat distribution, circulation
pump defect, valve closed / air in the
system,
Check the hydraulics
18
18
Er 37: Low pressure
Heat source insufficient, not enough re-
frigerant, expansion valve
Check the refrigerant circuit (OCHSNER)
16
16
Er 38: Hot gas
Expansion valve, insufficient refrigerant,
set value too high
Check the refrigerant circuit (OCHSNER)
10
10
Er 39: Motor protection
compressor
Motor protection relay, Phase er-
ror/overload, heat source temperature
too high
Check the compressor in refrigerant cir-
cuit (OCHSNER)
8
8
Er 42: Frost protection in
heat use system
Insufficient heat distribution, circulation
pump defect, valve closed / air in the
system, check the buffer pump or the
hydraulics