6.2
Temperature image
The hot water circuit temperature image gives an overview of the conditions and temper-
atures.
6.3
Operational data
The operational data can be seen in the hot water menu:
Operational data
Description
02-052 Status Hot Water
0 = Switched off
The hot water circuit is switched off.
the set value has been reached
1 = Normal charge mode
Charge to "05-051 normal hot water temperature"
2 = Comfort charge mode
Charging to "05-004 Legionella protection temperature°
5 = Fault
Hot water circuit malfunctioning
8 = Economy charge mode
Charge to "05-086 energy saving hot water temperature"
10 = Electric recharging
Charging via hot water auxiliary heater
11 = Charge aborted
Hot water charging terminated New start after temperature further
reduced.
00-004 Actual tempera-
ture hot water (TB)
The current hot water temperature is displayed.
01-004 Hot water setpoint
temperature
Current hot water set value is generated by the control and
is dependent on the operation selection/time program.
6.4
Relay test
The output status can be seen in the relay test.
Output status
Description
01-054 Hot water charge electro
0: Electro heating hot water OFF
1: Electro heating hot water ON
01-066 Switchover valve/ charge
pump hot water
0: Hot water charging with heat pump OFF
1: Hot water charging with heat pump ON
ESC
MENU
HOT WATER
Hot water charging via heat pump ON-OFF
Hot water charging via electrical rod ON-OFF
Hot water temperature (
TB
)