BA_OLW I OTE3_SW5x_EN_20160815_V2
12 / 48
►
Break out the breakout plate from the left hand side
panel using pliers.
► Thread the condensate drain hose to the left or right
from the appliance.
► Drain the condensate into a drain
If drainage into the ground is provided, lead the con-
densate hose through the breakout plate downwards
from the appliance.
1
Breakout plate "Durchführung Versorgungsleitung“
(supply pipework feed through)
Fig.14: Breakout plate for supply pipework
►
Lead the condensate drain hose at an
oblique angle through the hole in the "Durchführung
Versorgungs
leitung“ (supply pipework feed through)
►
Fix the condensate drain hose in such a way
that it cannot slip.
►
Drain
the
condensate
into
a
drain
6.5.1 Check the condensate drain
After laying the condensate hose, make sure that the
condensate is draining freely. Proceed as follows:
►
Pour water onto the evaporator so that it flows into
the de-icing sump. Ensure the maximum conden-
sate flow of 6l/min.
►
Check that the water drains away via the conden-
sate drain hose.
6.6 Flow rate measurement
The heat use system flow rate sensor is part of the
heat pump and must be
installed by the system installer according to the
OCHSNER installation instructions
.
Please observe the instructions for the adjustment of
the flow rate (see Annex 18.1 - adjustment
of the flow rate).
If the flow rate meter is either not installed,
or incorrectly installed, OCHSNER will
not
undertake the commissioning
of the sys-
tem.
OCHSNER accepts no liability for possible
damage which may occur if the flow rate
meter is either not installed, incorrectly in-
stalled, sized or wired up.
Fig.15: Flow meter installation in heating system
Содержание OLWI 9
Страница 2: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 2 48...
Страница 25: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 25 48 14 2 Hydraulic diagram...
Страница 26: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 26 48 14 3 Electric circuit diagrams OTE...
Страница 27: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 27 48...
Страница 28: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 28 48...
Страница 29: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 29 48 14 4 Wiring overview...
Страница 37: ...BA_OLW A I OTE3_SW5x_DE_20160510_V2 37 48 15 Declaration of Conformity...
Страница 38: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 38 48...
Страница 39: ...BA_OLW A I OTE3_SW5x_DE_20160510_V2 39 48 16 ERP Data...
Страница 40: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 40 48...
Страница 47: ...BA_OLW I OTE3_SW5x_EN_20160815_V2 47 48...