4.1.8 Hydraulic connection versions
CAUTION!
Do
not
set a night setback for the system as it is
designed to run uninterrupted during cold
temperatures in winter.
PLEASE NOTE
Due to the compressor output control, the heat
pump can be operated without a buffer tank.
CAUTION!
When using
individual room controllers
or if the
fill water capacity is less than 100 litres, for
heating/cooling application and when connected
to
Smart
Grid
,
a
buffer
tank
with
30 to 50 litres/kW is required depending on the
type of operation. If this buffer is not installed, the
system must be built according to schematic 7.1.1
or 7.2.1.
CAUTION!
The closures provided are only for transport.
Replace them with suitable plugs if the DHW flow
or return is not being used!
A buffer of at least 200 l is recommended for AIR
BASIC 416 and AIR BASIC 618 systems
(e.g.: Ochsner PU200). Size and install all WNA
pipe sizes according to the nominal flow rates.
Observe the limits of use as shown in the diagram.
In systems with cooling function, ensure adequate
insulation to prevent condensation.
For operational reliability, especially in defrosting
or cooling mode, it is important that the hydraulic
safety and pressure maintaining devices are
sufficiently sized and inspected annually according
to the relevant standards.
Rule of thumb: System charge pressure for heating
and cooling mode [bar] = DEV pre-charge pressure
+ 0.5 [bar].
NOTE
NOTE
Содержание AIR BASIC 109
Страница 2: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 2 of 92...
Страница 22: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 22 of 92...
Страница 34: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 34 of 92 Dimensions Figure 37 T200 dimensions...
Страница 78: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 78 of 92 11 4 Declaration of conformity...
Страница 79: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 79 of 92...
Страница 80: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 80 of 92...
Страница 81: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 81 of 92...
Страница 82: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 82 of 92 11 5 ERP Data...
Страница 83: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 83 of 92...
Страница 84: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 84 of 92...
Страница 85: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 85 of 92...
Страница 86: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 86 of 92...
Страница 87: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 87 of 92...
Страница 90: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 90 of 92...
Страница 91: ...BA_AIR_BASIC_ELW_Multitower_OTE3_SW5x_CC_EN_V08 docx Page 91 of 92...