Steam Generator Manual

7.3.  Water and Steam Connections

i.  The water supply pipe and steam pipe should comply with local standards

ii.  Connect the water inlet valve of the generator to the mains water supply using a flexible 

hose with 1/2 inch fittings. 

iii.  Steam outlet (1/2 inch or 3/4 inch) use the same dimension copper pipe to connect it, if the 

steam pipe is longer than 5 meter it should be insulated. During use the steam pipe will 

be very hot and must be protected against accidental contact. Note that according to the 

location it may be necessary to attach an additional length of pipe to the pressure relief valve 

in order to divert the steam flow to a safe direction should the valve operate.

iv.  Connect the drain outlet to a suitable drain via a copper pipe with the appropriate fittings.

7.4.  Installation for controller and temperature probe.

OC-D controller is waterproof and can be installed inside or outside the steam room according 

to customer preference.

i.  For a better connection and to eliminate any future connection problems spray connection 

fluid or aerosol oil spray on the pins of the PS/2 cable(5pin cable) before plugging into the 

circuit board. 

ii.  Ideally the control panel should be installed at a height of approximately 1200mm for ease of 

use. 

iii.  Installation method: Open the front cover of steam generator. Pin the control cable (6 cores) 

and temperature sensor cable (2 cores) to the relevant ports. 

iv.  Control panel installation: pin one end to circuit board ports in steam generator connect the 

other end to the controller’s cable.

v.  Temperature probe installation: the temperature probe is installed inside the steam room at 

approximately 1.2 to 1.5 meters high and away from the steam outlet. Use a 4mm screw fix it 

in place and then connect to the wire from the controller.

vi.  Fix protective cover (supplied) over the temperature

Temperature Sensor

4mm Screw

Cover to protect the temperature sensor

Содержание OCD-60

Страница 1: ...PRODUCT IMAGE Oceanic Ltd Pountney Street Wolverhampton WV2 4HX Phone 01902 450 550 sales oceanic saunas co uk www oceanic saunas co uk Sauna Steam Heavy Duty Commercial STEAM GENERATOR 15 06 17...

Страница 2: ...e 2 OC D Controller Parameters 8 5 7 Temperature Sensor Parameters 8 6 OC A Controller Description 9 7 Installation 10 7 1 Generator Size 10 7 2 Steam Generator Location 11 7 3 Water and Steam Connect...

Страница 3: ...as well as displaying the steam generator s status by the 8 LED s on the panel heating water inlet temperature drain status etc note also that one OC D controller can control multiple Oceanic steam g...

Страница 4: ...Sauna Steam Oceanic Saunas 01902 450 550 sales oceanic saunas co uk 4 Steam Generator Manual 4 Steam Generator Parts 4 3 2 1 9 8 7 6 5 10 15 11 11 12 13 14 17 18 19 20 16...

Страница 5: ...ction 9 Relay Circuit Board Electrically operated switches for elements 10 Overheat switch Boil dry protector operates at 105oC Use Pin to reset 11 Louvers Ventilation 12 Main Power Cable Entry Cable...

Страница 6: ...box has to be carried out by an authorised electrician In case of a warranty claim you are kindly requested to present a copy of the invoice from the electrician Model Power Current amps Size mm Stea...

Страница 7: ...e relief valve Operates if the pressure in the boiler exceeds 1 2kg c m2 Supplied 10 Brass T junction 3 4 to 3 4 and 1 2 brass fitting to fit steam pipe and pressure relief valve Supplied 11 Brass T 3...

Страница 8: ...Sauna Steam Oceanic Saunas 01902 450 550 sales oceanic saunas co uk 8 Steam Generator Manual 1 1 2 2 5 5 6 6 7 8 13 14 16 15 17 18 19 20 20 3 3 4 Jubilee clip cable tie Jubilee clip cable tie...

Страница 9: ...pipe Use a 3 4 female cap to block off the secondary outlet 9 9 10 13 13 13 10 12 11 5 2 Steam Pipe Connection Options Important note Steam outlet must not be reduced Mains in 230V 1N 400V 3N 230V li...

Страница 10: ...AVE J7 R CONTROL D9 J6 TEMP2 D8 D7 D6 D5 D4 D3 D2 D1 J4 NO NC Water Inlet AC power adapter AC230V DC24V Water Inlet Valve Drain Valve Descale Liquid Inlet Pump OC S Controller 2 r Circuit Diagram 2 4...

Страница 11: ...OCD 90 535 260 380 25 135 45 OCD 120 535 260 380 25 135 45 6 Parameters 6 2 Clearance distances 200mm 300mm 400mm 500mm A B C E D F 6 1 Steam Generator Frame Sizes 6 3 Ventilation Ensure air flow into...

Страница 12: ...D 30 60 o C 155 x 115 x 20 MODEL Detected Scope Max Cut out Temperature Size mm o C o F o C o F L W H OC S 0 110 32 230 60 248 76 42 27 6 4 Table 2 OC D Controller Parameters 6 5 Temperature Sensor P...

Страница 13: ...adequate guarding post a notice to caution users Keep the number of right angle bends to a minimum and ensure that the run does not create a trap into which condensate would gather and cause a blocka...

Страница 14: ...ace first then hang the generator by the 2 keyhole shaped holes in the back plate Then with the front cover removed fix the 3rd screw to secure the unit in place 10m The steam generator can be install...

Страница 15: ...ler and temperature probe OC D controller is waterproof and can be installed inside or outside the steam room according to customer preference i For a better connection and to eliminate any future con...

Страница 16: ...e main circuit board but you can add your own fused spur for extra protection if you prefer 7 7 Installing a Fan Same as above for a light 7 8 Connecting to descaler i OCD Generator is able to run aut...

Страница 17: ...o Water Supply 10 Generator Has Overheated 11 Fan On 12 Light On 13 Keypad Locked 14 Auto Timer Set 15 Fan On Decrease 16 Setting 17 Drain Must Be Off Increase 18 Light On Left Scroll 19 Machine On Of...

Страница 18: ...uttons to set the hours minutes and day 9 4 Setting Temperature i You can set the temperature between 35 and 600 C and between 95 and 1400 F ii If you are a novice user we advise to start at around 38...

Страница 19: ...am specfiic times for the generator to turn on and off throughout the day Once setup machine will remember to turn on or off at these same times everyday vi You can choose in the morning from between...

Страница 20: ...d it You must remember though that once the cycle has been completed you must turn the Tick to a X to turn the weekly descale off To setup descaling push Push to enter iv The default is Sunday between...

Страница 21: ...ng out of steam nozzle Water Level Probe Remove and clean water level probe Check connections to and from water level probe Check water pressure is 1bar Circuit breaker tripping out Element failure Lo...

Страница 22: ...the water for hardness and arrange the descaling routine accordingly High levels of hardness descale once every 50 to 100 hours of operation Medium levels of hardness descale once every 100 to 250 hou...

Отзывы: