2. (CAUSE) Thermostat
(REMEDY) Examine the control unit for loose wires. Tighten any loose connections. Wait 4-minutes
before re-start.
3. (REASON) High Pressure Control cutting turning unit off
(FIXING) Check for loose wire connections, broken or burned contacts. If switch is defective, replace.
Not enough water flow to unit or water is too warm.
4. (CAUSE) Compressor contactor open or burned.
(CURE) Replace
5. (REASON) Refrigerant leak no freon.
(REMEDY) Locate leak and repair. Evacuate unit and recharge.
6. (CAUSE) Loose or defective wires.
(FIXING) Tug on wires to see if they will separate from connections.
7. (REASON) Defective compressor
(REMEDY) Check for shorts, opens and grounds. Remove and replace compressor.
8. CAUSE) Shorted or open run capacitor
(FIXING) Remove and replace.
PROBLEM:
COMPRESSOR STARTS AND RUNS, BUT, FAN DOES NOT RUN.
1. (CAUSE) Faulty rocker switch
(REMEDY) Replace
2. (REASON) Open fan motor coil circuit
(FIXING) Replace fan motor.
3. (CAUSE) Shorted or open fan motor capacitor
(REMEDY) Replace capacitor.
4. (REASON) Loose or defective wires
(REMEDY) Trace and repair