OCEANAIRE DELUXE ELECTRONIC CONTROLLER
When power is connected, the controller will display “888” momentarily, and then
disappear. Press the POWER button, then scroll drown to the TEMP SELECT button
until the SET POINT is displayed. Adjust the SET POINT to the desired temperature,
and the unit will cool as required.
The systems controls temperature /- 2°
POWER
—
Turns the unit on/off when power is supplied
MODE
- Selects the mode of operation between Cool and Moisture Control.
COOL
- The system will operate in cooling mode only.
MOISTURE CONTROL
- The system operates in the cooling mode to reduce
humidity within the conditioned space.
Every 4 hours, the fan is started, circulating the air, and the air temperature is record-
ed by the controller. The cooling cycle is started for one hour, or until the room
temperature drops 2°, which ever comes first. This cycle repeats every four hours.
FAN SPEED
—
The operator can select between
AUTO or MANUAL
fan speed control.
Pressing the
FAN SPEED
button will switch speed from
AUTO to MANUAL
. In
MANUAL
mode, pressing the
FAN SPEED
button will change fan speed from low (1) to
high (6). In
AUTO
mode, the fan speed is controlled automatically. In cooling mode,
the controller automatically adjusts the fan speed to high, and as the inside tempera-
ture approaches the set point, the fan speed will decrease.
TEMP SELECT
—
Allows the operator to view the controller temperatures
INSIDE
= return air temperature,
DISCHARGE
= supply air temperature,
SET POINT
can be seen and adjusted, by pressing
▲
or
▼
.
The OWC1811QC controller is equipped with many features for a more precise level of
cooling and operation. With the addition of a remote sensor, the controller can sense
temperatures in another space or in ductwork. Doing that, you override the temperature
sensing bulb behind the evaporator grille.
POWER
button
DELUXE ELECTRONIC CONTROLLER
12
Содержание OWC1811QC
Страница 21: ...PIPING SCHEMATIC 19...
Страница 22: ...WIRING SCHEMATIC FOR OWC1811QC 20...