OCEANAIRE OWC1811QC Скачать руководство пользователя страница 19

TROUBLESHOOTING GUIDE 

 

The following steps and procedures are recommended for correcting the problems 

indicated. In the event that the problem can not be corrected, service may be required.  

 

SERVICE SHOULD BE PERFORMED BY A QUALIFIED AIR 

CONDITIONING SERVICE TECHNICIAN 

 

PROBLEM: UNIT DOES NOT POWER UP 

CAUSE:   

Power interruption 

REMEDY: 

Check LCDI and reset.  Check external power supply making sure that the 

disconnect is ON.  Check for blown fuses or tripped circuit breakers. Reset or replace 

(as needed). 

 

PROBLEM: NO DISPLAY ON THERMOSTAT AFTER POWER “ON”

 

CAUSE:  

Loose display cable, faulty thermostat or faulty power module 

REMEDY

: Check display cable, re-seat connectors.  Thermostat may be 

defective...remove and replace.  Power module may be defective...remove and replace. 

 

PROBLEM: EVAPORATOR FAN RUNS BUT COMPRESSOR DOES NOT 

START 

CAUSE:  

Thermostat 

 set point is too high.   

REMEDY:  

Make sure set-point is lower than room temperature. Look for a red dot to 

the right of the temperature displayed for cooling. 

 

Note

there is a time delay for the compressor 

 

CAUSE: 

Thermostat

Loose display cable 

REMEDY:  

Examine the thermostat for a loose cable connection. Re-seat the display 

cable from thermostat to power module. 

 

CAUSE:  

Condensate Alarm

—”CON” is displayed.

 

REMEDY:  

Check condensate pump and make sure pump is working properly and that 

there is no kink in the drain line from the pump.   

 

CAUSE:  

High Pressure Cut-Out

—”CON” is displayed.  Inadequate/turned off condenser 

water supply. 

REMEDY:  

Verify condenser water supply.  Check High Pressure Cut-Out Switch.  

Press Reset (RED Button in recessed cubby).  Re-start unit.   

 

CAUSE:  

Low Voltage 

 

“LAC” is displayed.  Check power supply for voltage outside 

the range of 106-126 volts. 

REMEDY:  

Have power checked by electrician and repaired. 

 

CAUSE: 

Compressor relay failure...fan relay failure      

REMEDY: 

Replace power module. 

17 

Содержание OWC1811QC

Страница 1: ...ENGINEERING INSTALLATION AND SERVICE MANUAL OWC1811QC 1 5 Ton Deluxe Portable Water Cooled Spot Cooler With Quick Connect EISM OWC1811QC 05012022...

Страница 2: ...In our ongoing process of continuous improvement the items and procedures described in this manual are subject to change without notice Please note model and serial number of the OWC1811QC unit when...

Страница 3: ...ected to the proper source of electrical power the OWC1811QC is controlled by a solid state electronic device with numerous op tions of temperature and airflow controls that will provide the desired l...

Страница 4: ...NNECT FITTING 1 4 LIFT VERTICAL 20 FT REFRIGERANT 18 oz R 410A HEIGHT 45 7 in WIDTH 21 5 in DEPTH 16 0 in NET WEIGHT 155 lb SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE Cooling capacity is total BT...

Страница 5: ...unit comes equipped with an Automatic Condensate Pump that removes the condensate The pump discharges through a check valve located on top of the conden sate pump assembly The vinyl tubing exits thro...

Страница 6: ...ed where it is needed A nozzle kit can be used to improve the velocity ROOM AIR CONDITIONER One feature of the OWC1811QC is it operates as a room air conditioner because water is used as the means for...

Страница 7: ...IOR Cubby for the Hose Kit High Pressure Switch Reset Button Drain Water In Electrical Cord Strain Relief Water Out Condensate Pump Access Door Condensate Pump Motor Thermostat Compressor Evaporator C...

Страница 8: ...on the back of the unit to confirm the proper power is available for the unit Refer to Specifications section for voltage and amperage requirements For the proper NEMA receptacle refer to Electrical s...

Страница 9: ...nclude edge guards By removing the OWC1811QC discharge grille the nozzle kit can then be installed in the grille opening Evaporator return air plenum is available for installations where it is require...

Страница 10: ...ening 2DDA 10 for OWC1811QC converts the evaporator discharge to a 10 inch diameter round duct When used in conjunction with the evapo rator return air plenum 2DEP 12 the unit can provide closed loop...

Страница 11: ...scharge to a drain A QC lanyard is supplied with each QC Coupling When engaged this device releas es the internal valve of the coupling allowing for air to break the vacuum and drain the hose All Hose...

Страница 12: ...ing 2 Connect WATER IN hose to water supply using hose connection and sink adapter if needed 3 Install WATER OUT line in drain allowing for free drain conditions with an air space around the opening 4...

Страница 13: ...stallation of a QC water cooled unit where the Standard QC Hose Kit cannot accommodate the installation The kit provides a means of connecting hoses to a QC Model unit when the water source and drain...

Страница 14: ...ever comes first This cycle repeats every four hours FAN SPEED The operator can select between AUTO or MANUAL fan speed control Pressing the FAN SPEED button will switch speed from AUTO to MANUAL In...

Страница 15: ...peed Limit Setting 30 55 P4 Temperature Sensor Calibration 10 P10 Temperature Display F or C P13 Supply Fan Operation Cycling or Continuous P1 P2 To adjust fan speed settings P1 represents the high fa...

Страница 16: ...742 hours 6 Add the 2 number sets together to get total hours 03 and 486 3486 hours 01 and 59 1059 hours TOTAL HOURS REPRESENTS COMPRESSOR RUN TIME MODEL CODE SETTINGS OWC1811QC P1 80 P2 50 OWC PROGRA...

Страница 17: ...n and close causing a harmonic pitch in the water supply line In these cases it is recommended that the water valve be adjusted 1 Disconnect the unit power 2 Remove water valve cover plate or back pan...

Страница 18: ...w controller and secure in place C POWER MODULE To remove the power module remove the rear control box cover Disconnect wires one at a time and re attach each wire while holding replacement module in...

Страница 19: ...NOT START CAUSE Thermostat set point is too high REMEDY Make sure set point is lower than room temperature Look for a red dot to the right of the temperature displayed for cooling Note there is a time...

Страница 20: ...en servicing pump follow these steps 1 Make certain that the unit is disconnected from the power source before attempting to service or remove any component 2 Be sure the floats move freely Clean as n...

Страница 21: ...PIPING SCHEMATIC 19...

Страница 22: ...WIRING SCHEMATIC FOR OWC1811QC 20...

Страница 23: ...ten instructions or has been altered or modified in any way b Product that has been subjected to any abnormal power conditions such as loss of power power surges voltage irregularities such as brown o...

Страница 24: ...___________________________ Purchased from _______________________________ Date Installed _________________________________ For Technical Support or service parts contact our Keep Cool Team at 847 583...

Отзывы: