its alarm state.
SMTP Mail Server Address
: The ip address of the email server on the LAN that will process and forward the
email message to the recipient.
Sender Address:
The address that will be used in the “From:” line of the email. This is helpful in identifying the
source of the alarm email message. If your SMTP mail server has junk filtering, you may be required to use a
sender address that matches a mailbox address on the SMTP mail server; check with your mail server
administrator for specific details on this issue.
Recipient address 1 (2,3):
The AcquiSuite can send a copy of the alarm notice to multiple email addresses.
Specify one, two or three email addresses in the fields provided for the recipient addresses.
Modbus Framework
The Modbus Framework feature is a tool to allow the AcquiSuite to read data from any Modbus device by
creating a template in the Modbus Framework editor. The template describes the Modbus register read
commands, and the conversion required for each data point that is to be read. The Framework feature is an
advanced feature of the AcquiSuite that requires the user to be familiar with the Modbus protocol and with the
Modbus register point list for the specific Modbus device that will be used. For more information on the
Modbus Framework feature, download the Modbus Framework documentation from www.obvius.com.
Wireless
Sensor List
The sensor list feature works in conjunction with a number of non-Modbus sensors. Sensor devices such as
PointSix, BAPI, and Badger/Orion typically transmit data on a pre-set interval and are not polled by the
AcquiSuite. Data is received and uniquely identified by the sensor's serial number. Each sensor may be given a
name, and some have additional options to configure such as input value scaling.
ModHopper Map
The AcquiSuite has additional diagnostic features that assist with ModHopper deployments. The most useful is
the ModHopper route map. Select the ModHoppers menu from the Wireless section in the AcquiSuite menu