Bypass Humidifiers
A bypass humidifier should be wired directly to the furnace or
fan coil HUM and 24VAC COM terminals. The Observer
Control will automatically energize the HUM output during a
call for humidification.
Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in or
der to energize upon a switch or contact closure. For this
application, a 24VAC N.O. Isolation Relay (DPST)
MUST
be
used to prevent mixing the internal humidifier power with the
indoor equipment transformer. Applying 24VAC isolation re
lay coil to furnace or fan coil HUM and COM terminals will
allow the Observer Control to automatically energize the
HUM output during a call for humidification. The N.O. relay
contacts will be used to energize the humidifier. See fan
powered humidifier installation instructions for more details.
Commissioning
Overview
This section addresses initial power up (or commissioning) of
an Observer Control. The wall control will communicate and
identify all communicating components in the system.
Содержание TSTAT0101SC
Страница 12: ...12 616 01 1017 02 2 Press under All Days then press EDIT...
Страница 13: ...13 616 01 1017 02 3 Press PERIOD then use the or to select the period to change...
Страница 27: ...27 616 01 1017 02...
Страница 31: ...31 616 01 1017 02 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no activity...
Страница 38: ...38 616 01 1017 02 Fan on with W An option to turn the fan on with a call for furnace heating ON OFF default...
Страница 67: ...67 616 01 1017 02 Defrost With Furnace Choose whether furnace operates during defrost cycle YES default NO...
Страница 74: ...74 616 01 1017 02...
Страница 81: ...81 616 01 1017 02 EInternational Comfort Products LLC PO Box 128 S Lewisburg TN 37091 USA...