11. Perform installation of all other system equipment (i.e.
humidifier, UV lights, etc.).
12. Turn on power to equipment.
NOTE:
In a dual fuel installation with a noncommunicating
heat pump, an OAT sensor must be installed, or the heat
pump will not run.
Shielded Wire
If the thermostat wiring will be located near or in parallel with
high voltage wiring, cable TV or Ethernet wiring, then shiel
ded thermostat wire can be used to reduce or eliminate po
tential interference. The shield wire should be connected to
the C terminal, or ground, at the indoor unit. The shield wire
should NOT be connected to any terminal at the wall control.
Connecting the shield to ground at both ends can cause cur
rent loops in the shield, reducing shield effectiveness.
Noncommunicating equipment
The Observer Control, when paired with the NAXA00101DB
daughter board, will operate noncommunicating equipment.
When the system utilizes the NAXA00101DB daughter
board, the Observer Control operates as a standard univer
sal thermostat. See Appendix Wiring Diagrams
Содержание TSTAT0101SC
Страница 12: ...12 616 01 1017 02 2 Press under All Days then press EDIT...
Страница 13: ...13 616 01 1017 02 3 Press PERIOD then use the or to select the period to change...
Страница 27: ...27 616 01 1017 02...
Страница 31: ...31 616 01 1017 02 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no activity...
Страница 38: ...38 616 01 1017 02 Fan on with W An option to turn the fan on with a call for furnace heating ON OFF default...
Страница 67: ...67 616 01 1017 02 Defrost With Furnace Choose whether furnace operates during defrost cycle YES default NO...
Страница 74: ...74 616 01 1017 02...
Страница 81: ...81 616 01 1017 02 EInternational Comfort Products LLC PO Box 128 S Lewisburg TN 37091 USA...