Ensure the system is free of dirt and foreign matter,

 

vented and isolated 

before any installation or 

servicing work is carried out.
The N-CNG is delivered ready for use. This 

installation must only be done by an authorised 

service engineer who is trained to ensure com-

pliance with all relevant national regulatory 

conditions. The nozzle is designed for the con-

nections as mentioned in 'Approvals / Operating 

conditions' and must not be used with any NPT 

or other thread sealing adapters. The designated 

connections do not require thread sealants.

Therefore, 

do not use

 PTFE sealing tape or 

liquid seal for any sealing as electrical conducti-

vity may be insufficient and particles of the tape 

commonly become loose and could clog the 

nozzle valve or damage vehicle motor parts.

This device complies with CSA/ANSI NGV 1-2017 

and ISO 14469:2017. The installation of this 

device shall conform to the requirements of the 

authorities having jurisdiction or, in the ab- 

sence of requirements, to NFPA 52 Standards, 

Compressed Natural Gas (CNG) Vehicular Fuel 

Systems, or CAN/CSA-B108, NGV Fuelling 

Stations Installation Code, as applicable.

Needed tools:

2 x Spanner with width of 23 mm / 7/8" 

2 x Spanner with width of 17 mm / 11/16"

1 x Spanner with width of 14 mm / 9/16"

1 x Foaming agents or spray bottle with snoop or soapy water

Check if connections correspond in type and 

size, e.g. JIC 37° 9/16-18" male / female

Remove caps from nozzle.

Connect the hoses to the nozzle. Torque the fill line 

to 45 Nm and torque the vent line to 35 Nm or as 

per hose fitting suppliers recommended tightening 

torque. 

Do not use pliers

.

Check sealing surfaces of connections at the 

nozzle as well as the hose assemblies.

4

DRAFT

Содержание N-CNG P30

Страница 1: ...ENGINEERING LIMITED 129 Birch Avenue Tauranga New Zealand Tel 64 07 928 38 08 Email info oasisngv com N CNG P30 P36 CSA ANSI NGV 1 2017 ISO 14469 2017 CNG NOZZLE INSTALLATION AND OPERATING MANUAL 22...

Страница 2: ...for public and private CNG refuelling stations The nozzle is designed to only allow gas to flow when it is correctly coupled and to not allow uncoupling from the vehicle refuelling receptacle when the...

Страница 3: ...f you suspect a leakage stop refuelling immediately use the emergency button to shut off the dispenser immediately evacuate the area and inform station personnel CNG Natural Gas is extremely flammable...

Страница 4: ...alve or damage vehicle motor parts This device complies with CSA ANSI NGV 1 2017 and ISO 14469 2017 The installation of this device shall conform to the requirements of the authorities having jurisdic...

Страница 5: ...escaping gas A small gas release upon uncoupling is normal If uncontrolled and or permanent gas release to the atmosphere occurs immediately stop fuelling If the leakage continues push emergency butto...

Страница 6: ...vehicle filling point OFF On completion of refuelling squeeze and release lever Latch will automatically release Fuelling should start automati cally OR has to be activated at the dispenser Please fol...

Страница 7: ...ny other common sense procedures generally applicable to equipment of this type The foregoing limitation extends to damages to person or property caused by the unit or damages resulting from the inabi...

Страница 8: ...serial number on the CNG nozzle bodies Excluded are nozzles and parts subjected to wear and tear and damages caused by improper use for example the use with unsuitable media Furthermore excluded are...