background image

20

4.10 . Parameter list and breakdown table

10.1 Electronic control fault table

    Can be judged according to the remote controller failure code and troubleshooting

4.Use and Operation Instruction

19

4.Use and Operation Instruction 

4.9.Fault interface

Keep long press 
of "       " for 5 s

4.8.Keyboard lock

To avoid others' misoperation, please lock the wire controller after completing 
the setting.

 

When the unit fails, the wire controller can display the corresponding code according to the 
fault reason. Refer to the fault table for the specific definition of the fault codes.

Notes: 

1).Under the locked screen interface, only unlocking operation is available, and the screen 

will  be lighten after other operations conducted. 

2).Under the OFF interface, locking operation is available , and the operation method is the 

same as locking screen under the ON interface.

 

2).Two or more faults:

1).Single fault:

Short press"      " 
or "      "

Fault code

Fault serial number

Quantity of fault

Short press"       "

For example:

Notes: 
1). When the silent icon"       " is lighten:The timing mute has been set, but it's not under silent 
status.
2). When the silent icon"       " flash:It's under the silent status.
3). When the silent icon"       "disappear: The timingsilent is not set.

Remark: 

The wire controller can display the temperature unit as "

" or "

" according to the unit

model you bought.

Protect/fault

Amibent Temp. Sensor Fault

Outlet Temp. Sensor Fault

Coil 1 Temp. Sensor Fault

Winter Secondary A

  nti-freezing

Prot.

Anti-freezing Prot.

Suction Temp. Sensor Fault

Low Pressure Prot.

Flow Switch Prot.

Inlet and outlet temp. too big

Coil 2 Temp. Sensor Fault

Discharge Temp. Sensor
Fault

High Pressure Prot.

Exhaust  Air over Temp Prot.

Comp. Overcurrent Prot. 

Communication Fault

Winter Primary  Anti-freezing 
Prot.

Fault 

display

P01

P02

P04

P05

P07

E02

E07

E03

E29

E06

P15

P081

E051

E08

E19

E01

P082

Reason

Elimination methods

Antifreeze Temp. Sensor Fault

Waterway Anti-freezing Prot.

EC fan feedback Fault

P09

E05

F051

Check the wire connection  between 
remote wire controller and main board 

Check whether the system of the compressor 
running normally

Check whether the system of the compressor 
running normally

Check the pipe water flow and whether 
water system is jammed or not

Check or change the   temp. Sensor

Check the pipe water flow and whether

 

 

 

 

 

 

 

water system is jammed or not

 

   

 

 

Check the pipe water flow and water pump

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check the pressure switch and cold circuit

Check or change the   temp. Sensor

Check the pressure switch and cold circuit

check and replace this temp sensor

Check whether fan motor is broken or locked 
or not

Inlet Temp. Sensor Fault

PP

Pressure sensor Fault

The temp. Sensor is broken 
or short circuit

The temp. Sensor is broken 
or short circuit

The temp. Sensor is broken
or short circuit

The temp. Sensor is broken
or short circuit

The ambient temp. Is low in winter

Water flow is not enough 
and low differential pressure

The temp. Sensor is broken
or short circuit

Water flow is not enough

The temp. Sensor is broken 
or short circuit

Low pressure1  protection

No water/little water in 
water system

The temp. Sensor is broken 
or short circuit

The high-preesure switch is
 broken

The compressor is overload 

The ambient temp. Is low in winter

Communicat ion failure between 

 

 

 

wire controller and mainboard

The compressor is overload 

Antifreeze temp sensor is
 broken or short circuited

 Water temp.or ambient temp.
 is too low

There is something wrong with fan
 motor and fan motor stops running

The pressure Sensor is broken 

F031

Fan Motor1 Fault

1. Motor is in locked-rotor state
2.The wire connection between 
DC-fan motor module and fan 
motor is in bad contact

1.Change a new fan motor
2.Check the wire connection and make sure 
they are in good contact

Check or change the   pressure  Sensor
or pressure

TP

Ambient temp is too low

Low AT Protection

E081

Communication Fault
(speed control module)

Speed control module and main 
board communication fail

 

 

 

 

Check the communication connection

Содержание I19

Страница 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Страница 2: ......

Страница 3: ...ch 4 5 4 6 4 7 Silent 4 8 4 9 4 10 4 11 Main board 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Parameter list and breakdown table Cable specific...

Страница 4: ...mming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Dur...

Страница 5: ...The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Applia...

Страница 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Страница 7: ...oise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight Nominal Heating Capacity kW Btu h kW Btu h kW kW A A W R...

Страница 8: ...antity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net...

Страница 9: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Modles Oasis I9 Oasis I12 unit mm 2 SPECIFICATION 6 545 956 1000 398...

Страница 10: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Models Oasis I19 unit mm 2 SPECIFICATION 7 Water inlet 40 Water outlet 40 96 790 490 862 466 1115 1160 467...

Страница 11: ...teps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary t...

Страница 12: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Страница 13: ...o the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand a...

Страница 14: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Страница 15: ...ed to enter and exit the mute mode with one click 4 2 Key and icon function instruction Key symbols It is used to switch the unit mode temperature setting and parameter setting It is used to carry out...

Страница 16: ...the unit It will display when compressor is started It will display when water pump is started It will display when fan is started When the timing mute function is started it keeps bright for a long...

Страница 17: ...shut down the wire controller will display as follows Operations are the same as under ON OFF main interface 4 4 Mode switch Under the main interface Short press to switch the unit among heating cooli...

Страница 18: ...When the unit is under the defrosting state the defrosting symbol is on with the display interface as follows Notes 1 After completing the defrosting the unit will be automatically switched to the hea...

Страница 19: ...erating steps the changes will not be saved and return to the main interface Under the clock setting interface Long press for 2 s to enter into the system times setting interface Short press Press or...

Страница 20: ...interface Notes 1 Under the Timer ON OFF setting interface if there is no operation for 20 s the system will automatically memorize user s settings and return to the main interface 2 Under the Timer O...

Страница 21: ...p long press of for 2 s Short press or Short press for entering the hour digit setting of timing on silent Short press or Short press for confirming the timing on silent and turn to the setting of tim...

Страница 22: ...nd the screen will be lighten after other operations conducted 2 Under the OFF interface locking operation is available and the operation method is the same as locking screen under the ON interface 2...

Страница 23: ...sor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and cold circuit check and replace this temp sensor Check whether fan motor is broken or locked...

Страница 24: ...nt Check the input voltage measurement Check the input voltage measurement Check and adjust the current measurement Check the communication connection Check the PFC switch tube short circuit or not Ch...

Страница 25: ...n Instruction 10 2 Parameter list Meaning 28 28 27 Remarks Adjustable Adjustable Adjustable Default Refrigeration target temperature set point Heating the target temperature set point Automatic target...

Страница 26: ...23 Controller interface diagram and definition 4 11 Main board Oasis I9 I12 4 Use and Operation Instruction 1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 1 2 ACN1 ACL1...

Страница 27: ...1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 Controller interface diagram and definition 4 11 Main board Oasis I19 24 4 Use and Operation Instruction 1 2...

Страница 28: ...put Water output temperature input System fan coil temperature input Ambient temperature input System Exhaust temperature input Earth wire Earth wire System suction temperature input Water input tempe...

Страница 29: ...Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shall b...

Страница 30: ...times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to instal...

Страница 31: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Страница 32: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Страница 33: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Страница 34: ...line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm...

Страница 35: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Страница 36: ...33 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I9 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Страница 37: ...e switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat ex...

Страница 38: ...35 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I12 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Страница 39: ...re switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat e...

Страница 40: ...6 APPENDIX 6 3 Explosive view of the unit 37 Moddel Oasis I19 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Страница 41: ...Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat exchanger...

Страница 42: ...Note...

Страница 43: ......

Страница 44: ...Code 20190508 0001...

Отзывы: