background image

Charging procedures
In addition to conventional charging procedures, the following requirements shall be 
followed.

 Ensure that contamination of different refrigerants does not occur when using charging 

equipment. Hoses or lines shall be as short as possible to minimise the amount of 
refrigerant contained in them.

 Cylinders shall be kept upright.

 Ensure that the refrigeration system is earthed prior to charging the system with 

refrigerant.

 Label the system when charging is complete (if not already).

 Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system it shall be pressure tested with OFN. The system shall be 
leak tested on completion of charging but prior to commissioning. A follow up leak test shall 
be carried out prior to leaving the site.

Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar 
with the equipment and all its detail. It is recommended good practice that all refrigerants 
are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall 
be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential 
that electrical power is available before the task is commenced. 
a) Become familiar with the equipment and its operation. 
b) Isolate system electrically. 
c) Before attempting the procedure ensure that: 
. Mechanical handling equipment is available, if required, for handling refrigerant cylinders; 
. All personal protective equipment is available and being used correctly; 
. The recovery process is supervised at all times by a competent person; 
. Recovery equipment and cylinders conform to the appropriate standards. 
d) Pump down refrigerant system, if possible. 
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from 
various parts of the system. 
f) Make sure that cylinder is situated on the scales before recovery takes place. 
g) Start the recovery machine and operate in accordance with manufacturer's instructions. 
h) Do not overfill cylinders. (No more than 80 % volume liquid charge). 
i) Do not exceed the maximum working pressure of the cylinder, even temporarily. 
j) When the cylinders have been filled correctly and the process completed, make sure that 
the cylinders and the equipment are removed from site promptly and all isolation valves on 
the equipment are closed off. 
k) Recovered refrigerant shall not be charged into another refrigeration system unless it 
has been cleaned and checked. 

30

5. MAINTENANCE AND INSPECTION

5. MAINTENANCE AND INSPECTION

The safety wire model is  5*20_5A/250VAC,And must meet the explosion-proof 
requirements

29

Removal and evacuation 
When breaking into the refrigerant circuit to make repairs  or for any other purpose 
conventional procedures shall be used. However, it is important that best practice is 
followed since flammability is a consideration. The following procedure shall be adhered to: 
. Remove refrigerant; 
. Purge the circuit with inert gas; 
. Evacuate; 
. Purge again with inert gas; 
. Open the circuit by cutting or brazing. 
The refrigerant charge shall be recovered into the correct recovery cylinders. The system 
shall be "flushed" with OFN to render the unit safe. This process may need to be repeated 
several times. Compressed air or oxygen shall not be used for this task. 
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing 
to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling 
down to a vacuum. This process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented down to atmospheric 
pressure to enable work to take place. This operation is absolutely vital if brazing 
operations on the pipe-work are to take place. 
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available. working on them. 

5. MAINTENANCE AND INSPECTION

5. MAINTENANCE AND INSPECTION

Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of 
refrigerant. The label shall be dated and signed. Ensure that there are labels on the 
equipment stating the equipment contains flammable refrigerant. 

Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is 
recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant 
recovery cylinders are employed. Ensure that the correct number of cylinders for holding
the total system charge is available. All cylinders to be used are designated for the 
recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery 
of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-
off valves in good working order. Empty recovery cylinders are evacuated and, if possible, 
cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions 
concerning the equipment that is at hand and shall be suitable for the recovery of 
flammable refrigerants. In addition, a set of calibrated weighing scales shall be available 
and in good working order. Hoses shall be complete with leak-free disconnect couplings 
and in good condition. Before using the recovery machine, check that it is in satisfactory 
working order, has been properly maintained and that any associated electrical 
components are sealed to prevent ignition in the event of a refrigerant release. Consult 

manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct 
recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants 
in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been 
evacuated to an acceptable level to make certain that flammable refrigerant does not 
remain within the lubricant. The evacuation process shall be carried out prior to returning 
the compressor to the suppliers. Only electric heating to the compressor body shall be 
employed to accelerate this process. When oil is drained from a system, it shall be carried 
out safely.

Содержание I19

Страница 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Страница 2: ......

Страница 3: ...ch 4 5 4 6 4 7 Silent 4 8 4 9 4 10 4 11 Main board 5 Maintenance and Inspection 6 Appendix Installation illustration Swimming Pool Heat Pumps Location Parameter list and breakdown table Cable specific...

Страница 4: ...mming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Dur...

Страница 5: ...The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Applia...

Страница 6: ...eparately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs T...

Страница 7: ...oise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net Weight Shipping Weight Nominal Heating Capacity kW Btu h kW Btu h kW kW A A W R...

Страница 8: ...antity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Ship Dimensions L W H Net...

Страница 9: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Modles Oasis I9 Oasis I12 unit mm 2 SPECIFICATION 6 545 956 1000 398...

Страница 10: ...2 2 The dimensions for Swimming Pool Heat Pump Unit Models Oasis I19 unit mm 2 SPECIFICATION 7 Water inlet 40 Water outlet 40 96 790 490 862 466 1115 1160 467...

Страница 11: ...teps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary t...

Страница 12: ...us source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool T...

Страница 13: ...o the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand a...

Страница 14: ...our pool pump is running when the pool temperature drops more than 0 2 below set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect cont...

Страница 15: ...ed to enter and exit the mute mode with one click 4 2 Key and icon function instruction Key symbols It is used to switch the unit mode temperature setting and parameter setting It is used to carry out...

Страница 16: ...the unit It will display when compressor is started It will display when water pump is started It will display when fan is started When the timing mute function is started it keeps bright for a long...

Страница 17: ...shut down the wire controller will display as follows Operations are the same as under ON OFF main interface 4 4 Mode switch Under the main interface Short press to switch the unit among heating cooli...

Страница 18: ...When the unit is under the defrosting state the defrosting symbol is on with the display interface as follows Notes 1 After completing the defrosting the unit will be automatically switched to the hea...

Страница 19: ...erating steps the changes will not be saved and return to the main interface Under the clock setting interface Long press for 2 s to enter into the system times setting interface Short press Press or...

Страница 20: ...interface Notes 1 Under the Timer ON OFF setting interface if there is no operation for 20 s the system will automatically memorize user s settings and return to the main interface 2 Under the Timer O...

Страница 21: ...p long press of for 2 s Short press or Short press for entering the hour digit setting of timing on silent Short press or Short press for confirming the timing on silent and turn to the setting of tim...

Страница 22: ...nd the screen will be lighten after other operations conducted 2 Under the OFF interface locking operation is available and the operation method is the same as locking screen under the ON interface 2...

Страница 23: ...sor Check the pressure switch and cold circuit Check or change the temp Sensor Check the pressure switch and cold circuit check and replace this temp sensor Check whether fan motor is broken or locked...

Страница 24: ...nt Check the input voltage measurement Check the input voltage measurement Check and adjust the current measurement Check the communication connection Check the PFC switch tube short circuit or not Ch...

Страница 25: ...n Instruction 10 2 Parameter list Meaning 28 28 27 Remarks Adjustable Adjustable Adjustable Default Refrigeration target temperature set point Heating the target temperature set point Automatic target...

Страница 26: ...23 Controller interface diagram and definition 4 11 Main board Oasis I9 I12 4 Use and Operation Instruction 1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 1 2 ACN1 ACL1...

Страница 27: ...1 2 3 1 2 1 2 A B 1 2 1 2 4 5 6 3 1 2 4 5 6 3 1 2 1 2 1 2 4 5 6 3 7 8 9 Controller interface diagram and definition 4 11 Main board Oasis I19 24 4 Use and Operation Instruction 1 2...

Страница 28: ...put Water output temperature input System fan coil temperature input Ambient temperature input System Exhaust temperature input Earth wire Earth wire System suction temperature input Water input tempe...

Страница 29: ...Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed Work procedure Work shall b...

Страница 30: ...times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to instal...

Страница 31: ...sphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into a...

Страница 32: ...e that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylin...

Страница 33: ...le before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is avai...

Страница 34: ...line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm...

Страница 35: ...emperature R410A Pressure MPa Temperature R32 Temperature R410A Temperature R32 0 0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 51 3 20 9 4 11 19 24 31 35 39 52 5 20 9 3 5 10 18 23...

Страница 36: ...33 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I9 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Страница 37: ...e switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat ex...

Страница 38: ...35 6 APPENDIX 6 3 Explosive view of the unit Moddel Oasis I12 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Страница 39: ...re switch Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat e...

Страница 40: ...6 APPENDIX 6 3 Explosive view of the unit 37 Moddel Oasis I19 Complete machine structure explosion diagram Electrical control structure explosion diagram...

Страница 41: ...Needle valve Pressure switch Water flow switch There way valve Electronic expansion valve There way valve Filter Four way valve Junction box body Right side of the plate Titanium tube heat exchanger...

Страница 42: ...Note...

Страница 43: ......

Страница 44: ...Code 20190508 0001...

Отзывы: