Oasis SmartChem - INSTALLATION AND OPERATION MANUAL
Page
12
of
22
Chemical Balance (continued)
When ORP is highlighted, the Chemical Balance window will display;
1.
Whether the ORP is Low, Normal, or High.
2.
What the actual ORP level is currently.
3.
What the Set Point for ORP is set to achieve.
NOTES:
•
A low ORP reading indicates that the pool water may be carrying live
and potentially dangerous germs that could make swimmers ill.
•
A high ORP reading could lead to swimwear being bleached and could
also irritate the skin and eyes of swimmers.
Diagnostics
If your Pool/Spa systems water is not balanced correctly, you may see the following on the home screen
of the App.
What the
Oasis SmartChem
is displaying is the following;
1.
The pH reading is outside of the systems reading range of 5.5
to 8.5. If the reading is lower than 5.5 (<5.5) or higher than
8.5 (>8.5), the controller won’t dose Acid and will display
CHECK in the pH box.
If the system is displaying CHECK, you will need to take a
sample of your pool water to your local pool shop and get it
tested and add the amount of Acid or Buffer required to get
the pH level back to where it needs to be (7.2
– 7.8).
If the system is displaying ---, it indicates that there may be a fault with
the probe itself or indicates an invalid reading.
2.
The ORP reading is outside of the systems reading range of
300mV to 800mV. If the reading is lower than 300mV (<300)
or higher than 800mV (>800), the controller won’t Chlorinate
and will display CHECK in the ORP box.
If the system is displaying CHECK, you will need to take a
sample of your pool water to your local pool shop and get it
tested and either;
a. add the correct amount of Chlorine required to get the ORP level back to where it needs
to be (about 650mV), or
b. stop chlorinating the pool for a certain amount of time to allow the chlorine level to lower.
If the Chlorine level is to high, a Chlorine Reducer chemical can be added to the pool to
reduce the Chlorine level.
If the system is displaying ---, it indicates that there may be a fault with the probe itself or indicates an
invalid reading.