11990-190/192
Thermals
29
R1.0, October 2018
7.5 Rear Board Air Distribution
The airflow is measured with impedance boards acc. to the PICMG 3.0 R3.0
specification.
•
Rear board pressure drop: 24 Pa at 0.14 m³/min
Figure 23: Rear Board Air Distribution 11990-190
Figure 24: Rear Board Air Flow 11990-190