27
Ambient temperature
influence
≤
100 ppm/K
Deviation below/above
the measuring range
According to NAMUR recommendation
NE 43 (only current input 4 to 20 mA)
Sampling rate
150 ms
Input filter
Digital filter, 2nd order; filter constant
can be set from 0 to 100.0 s
Measuring circuit monitoring
The device behavior in the event of a fault is configurable.
Measuring
probe
Measuring
range
underflow
Measuring
range
overflow
Short-circuit
(probe/line)
Break
(probe/
line)
Polarity
RTD
temperature
probe
++
++
++
++
---
Resistance/
potentiometer
---
++
---
++
---
Resistance
transmitter
---
++
(+)
a
(+)
b
---
Thermo+
++
---
++
(+)
c
Current
0 to 20 mA
---
++
---
---
---
Current
4 to 20 mA
++
++
++
++
++
Voltage 0 to
10 V
---
++
---
---
++
Voltage 2 to
10 V
++
++
++
++
++
++ = is detected
--- = is not detected
(+) = is detected in
certain conditions
a
Is not detected in all combinations
b
Break in measuring current path is not detected
c
Dependent on the set characteristic line
5.2
Digital inputs
Input for potential-free
contact
Function
Sampling rate
Contact closed: input is active (RON < 1 kΩ)
Contact open: input is inactive (ROFF > 50 kΩ)
150 ms