28
|
5.3
Analog outputs
Voltage
Output signal
Load resistance
DC 0(2) to 10 V
> 500 Ω
Current
Output signal
Load resistance
DC 0(4) to 20 mA
< 450 Ω
Accuracy
≤ 0.5 %
Ambient temperature
influence
≤ 150 ppm/K
5.4
Digital outputs
Relay (N/O contact)
Switching capacity
Contact life
Max. 3 A at AC 230 V or DC 30 V, resistive load
150,000 operations at rated load
350,000 operations at 1 A
Relay (N/O contact) with
longer contact life
Switching capacity
Contact life
Max. 3 A at AC 230 V, resistive load
300,000 operations at rated load
1,500,000 operations at 1 A
Logic output
Output signal
Current
Switching time when used
as a controller output
DC 0/14 V
±
15 %
Max. 20 mA per output (at nominal voltage 14 V)
Min. 10 ms
PhotoMOS
®
relay
a
Switching capacity
Max. 200 mA at AC 30 V or DC 45 V;
not short-circuit proof
a
PhotoMOS is a registered trademark of Panasonic Corporation.
Содержание 00123456
Страница 1: ...TCONTROL 05 PANEL MOUNTED CONTROLLER...