24
|
5.
Technical data
5.1
Analog input
Thermocouples
Designation Type Standard
ITS
Measuring
range
Accuracy
a
Fe-CuNi
"L"
DIN 43710
(1985)
IPTS-68 –200 to
+900°C
≤
0.25 %
Fe-CuNi
"J"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–210 to
+1200°C
≤
0.25 % from
-100°C
Cu-CuNi
"U"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
IPTS-68 –200 to
+600°C
≤
0.25 % from
-100°C
Cu-CuNi
"T"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–270 to
+400°C
≤
0.25 % from
-150°C
NiCr-Ni
"K"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–270 to
+1300°C
≤
0.25 % from
-80°C
NiCr-CuNi
"E"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–270 to
+1000°C
≤
0.25 % from
-80°C
NiCrSi-NiSi "N"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–270 to
+1300°C
≤
0.25 % from
-80°C
Pt10Rh-Pt
"S"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–50 to
+1768°C
≤
0.25 % from
20°C
Pt13Rh-Pt
"R"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–50 to
+1768°C
≤
0.25 % from
50°C
Pt30Rh-
Pt6Rh
"B"
DIN EN 60584-
1:2014
IEC 60584-
1:2013
ITS-90
–50 to
+1820°C
≤
0.25 % from
400°C