13
Displaying and changing program settings
To view or access the settings
To access folder menus:
1. Press
button to display passcode screen, the screen displays
PSd
on line
1
and
0000
on line
2
.
2. Press
button to access to passcode , the first digit of
0000
is flashing and press
3
more times until the last digit of
0000
flashes.
3. Press
arrow two times to change the
0
to
2
. Press
for access to folder menus.
Note:
to exit the security level to the main screen wait one minute with no action or Press
arrow until
LOG Out
message displays, then
press
button.
To change a parameter setting
1. Once in the folder menu navigate to the desired setting to be changed using the
arrow to scroll and
button to access a menu or
parameter.
2. To change a parameter Press
button and parameter value will begin to flash.
3. Press
/
arrow to the desire value.
4. Press
button to save the setting and the screen will revert to the parameter mnemonic.
Note:
if
button is not pressed, the new setpoint is not saved.
To exit the parameter settings to the main screen wait one minute with no action or Press
arrow few times until
ESC
displays, then press
button to return to
UoF
screen. From the
UoF
screen Press
arrow few times until
LOG Out
message displays, then press
button to
return to the main screen.
Selecting
ESC
returns to folder menu.
Selecting
LOG out
returns to main screen.
Heat/cool operating parameters
Mnemonic Parameter
Description
Default Value
Range
CSt
1
Cooling setpoint
80
F
26
.
7
C
72
F to
120
F
22
.
2
to
48
.
9
C
Cd (Cd
1
)
1
Cooling differential
7
F
3
.
9
C
2
F to
25
F
1
.
1
to
13
.
9
C
Cd
2
4
Cooling differential
2
15
F
8
.
3
C
HSt
2
3
Heating setpoint
50
F
10
.
0
C
45
F to
60
F
25
.
0
to
33
.
3
C
Hd
3
Heating differential
7
F
3
.
9
C
2
F to
25
F
1
.
1
to
13
.
9
C
1. Compressor or cooling turns ON at CSt + Cd and OFF at CSt
2. Heater or heating turns ON at HSt and OFF at HSt + Hd
3. Heating mode is only applied to a unit with heater option
4. Cooling differential
2
is only applied to
2
-stage compressor and lead-lag application
Alarm parameters
Mnemonic Para
Description
Default value
Ht
High temperature alarm setpoint
125
F
51
.
7
C
Lt
Low temperature alarm setpoint
40
F
4
.
4
C
dO
Door open alarm setting
NC
ArOP
Alarm relay output
NO
Note:
(
4
) The alarm relay output logic is designed to be configurable