4
|
RECEIVING THE AIR CONDITIONER
Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents, scratches, loose
assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention
of the delivering carrier -- NOT to nVent Equipment Protection -- within
15
days of delivery. Save the carton and packing material and request
an inspection. Then file a claim with the delivering carrier.
nVent Equipment Protection cannot accept responsibility for freight damages; however, we will assist you in any way possible.
HANDLING AND TESTING THE AIR CONDITIONER
If the air conditioner has been in a horizontal position, be certain it is placed in an upright, vertical or mounting position for a minimum of
five (
5
) minutes before operating.
CAUTION:
Do not attempt to operate the air conditioner while it is horizontal or on its side, back or front. The refrigeration compressor is filled with
lubricating oil. This will cause permanent damage to the air conditioner and also voids the warranty.
Test for functionality before mounting the air conditioner to the enclosure.
Refer to the nameplate for proper electrical current requirements, and then connect the power cord to a properly grounded power supply.
Minimum circuit ampacity should be at least
125
% of the amperage shown in the design data section for the appropriate model. No other
equipment should be connected to this circuit to prevent overloading.
Operate the air conditioner for five (
5
) to ten (
10
) minutes. No excessive noise or vibration should be evident during this run period. The
condenser blower (ambient air), the evaporator blower (enclosure air), and the compressor should be running.
Condenser air temperatures should be warmer than normal room temperatures within a few minutes.
The compressor is provided with automatic reset thermal overload protection. This thermo-switch is located and mounted inside the plastic
enclosure clipped to the compressor. The switch operates when the compressor overheats due to clogged or dirty inlet air filter or if ambient
air temperatures exceed nameplate rating or if enclosure dissipated heat loads exceed the rated capacity of the air conditioner. The thermal
overload switch will actuate and stop compressor operation. The blowers will continue to operate and the compressor will restart after it has
cooled to within the thermal overload cut-in temperature setting.
Содержание X2302
Страница 1: ...Extreme AC Air Conditioner X2302 Model Instruction Manual P N 89215748 Rev E...
Страница 2: ......
Страница 7: ...nVent com HOFFMAN 7 Wire diagram 89206067 REV C...
Страница 8: ...8 nVent com HOFFMAN Schematics 89206866 REV B J3...
Страница 12: ...12 nVent com HOFFMAN...