Isolation - Before commencing work make sure
that the unit is electrically isolated from the mains supply.
Note: internal input socket will be exposed and may be
live with the fan module removed. See isolation notes.
MEV-B
Continuous Mechanical Extract
Ventilation Units
Installation and Maintenance
1
24. 06. 13. Leaflet Number 671078
Introduction
Nuaire's MEV-B and MEV-2B surface mounted domestic
extract fans are designed to be installed in the main area to
be served.
Other adjoining rooms can be linked to the unit by rectangular
pvc ducting (by others) and ventilated. A typical installation
would be in a domestic kitchen with secondary ventilation to
toilet(s), utility room(s) and bathroom(s) etc.
The unit is available in single and twin fan models coded B and
2B respectively.
The fans discharge air through a 125mm. dia. spigot on the rear
face. Inlet is through filters located on the either side of the unit
and/or filters in the remote grilles which can easily be removed
for cleaning. Also provided are two subsidiary inlet spigots
which are interchangeable with the inlet grilles in the unit and a
choice of balancing plates which can be introduced under any of
the inlet filters to adjust the airflow from each source.
Fig. 1 shows the subsidiary spigots fitted either side.
Two indicator LEDs are provided on the front cover to show fan
status, GREEN for ‘Normal / Boost’ and RED for ‘Fail’.
The fan is designed to be wired direct to the mains supply
through a fused spur isolator (by others) and run continuously
in the NORMAL mode (which is the low speed or trickle
ventilation setting). The degree of extract from each room served
can be adjusted with the inlet grille balancing plates supplied.
(See page 2).
The unit is provided with adjustment for the trickle (low speed
or NORMAL) and high speed BOOST ventilation as standard.
The NORMAL speed adjustment has a range of 0% to 50%.
The unit is delivered with the NORMAL speed adjustment set to
0%.
Note: the NORMAL speed must be set to 25% by the
installer.
An adjustment of 50 -100% is provided for the BOOST duty
setting to reduce performance if necessary.
The unit is delivered with the BOOST speed adjustment set to
100%. (See the adjustments information on page 4).
Coding
MEV-B
Single fan unit.
MEV-2B
Twin fan unit (with auto duty sharing and standby).
MEV- B+
Dual fan unit (both fans continuous running).
Duty
Units are available with one or two fans and with the following
free air duty:
100 l/s (MEV-B & MEV-2B).
The MEV-B has a single fan and extracts 100 l/s.
The MEV-2B has two fans and extracts 100 l/s. The unit will
switch to the ‘standby’ fan in the event of a fan failure.
150 l/s (MEV-B+).
The MEV-B+ has two fans which run continuously and deliver
150 l/s. In the event that one fan fails, the other will still deliver
100 litres as a single fan until the unit is serviced.
Typical mounting arrangements
The unit is designed for surface mounting onto a wall or ceiling.
Suggested layout arrangements with the fan serving multiple
rooms are shown on page 3.
Installation
IMPORTANT
The installation must be carried out by competent personnel
in accordance with the appropriate authority and conforming
to all statutory and governing regulations, ie IEE, COHSE, HVCA
etc.
Select a solid, non reverberant, mounting position (min. 50mm
clearance from any sidewall and min. 50mm from ceiling for
access to the top cover screw). The unit should be fitted with its
filters and any chosen inlet spigots. All necessary passages for
ductwork from the rear outlet and any inlet spigots as well as
the electrical connections for the main unit and the remote
switch, should be prepared.
It is assumed that compatible ductwork has been installed and
ready to be connected to the 125mm dia rear outlet (and any
rectangular inlet spigot if fitted) of the unit.
Note the unit is not fitted with a backdraught shutter.
In continuous operation a backdraught shutter is not
required.
Figure 1. General view of unit.
Wall tube and
fixed louvre grille
(by others).
Wall tube and
fixed louvre
grille
(by others).
125 circular
ducting (by others)
Fan Ceiling Mounting
Fan Wall Mounting
Figure 2. Fan unit mounting arrangements.
The EMC Directive
2004/108/EC
The Low Voltage
directive
2006/95/EC