Isolation - Before commencing work make sure

that the unit is electrically isolated from the mains supply.

Note: internal input socket will be exposed and may be 

live with the fan module removed. See isolation notes. 

MEV-B 

Continuous Mechanical Extract 
Ventilation Units

Installation and Maintenance

1

24. 06. 13. Leaflet Number 671078

Introduction

Nuaire's MEV-B and MEV-2B  surface mounted domestic

extract fans are designed to be installed in the main area to

be served.

Other adjoining rooms can be linked to the unit by rectangular

pvc ducting (by others) and ventilated. A typical installation

would be in a domestic kitchen with secondary ventilation to 

toilet(s), utility room(s) and bathroom(s) etc.

The unit is available in single and twin fan models coded B and

2B respectively.

The fans discharge air through a 125mm. dia. spigot on the rear

face. Inlet is through filters located on the either side of  the unit

and/or filters in the remote grilles which can easily be removed

for cleaning.  Also provided are two subsidiary inlet spigots

which are interchangeable with the inlet grilles in the unit and a

choice of balancing plates which can be introduced under any of

the inlet filters to adjust the airflow from each source. 

Fig. 1 shows the subsidiary spigots fitted either side.

Two indicator LEDs are provided on the front cover to show fan

status,  GREEN for ‘Normal / Boost’ and RED for ‘Fail’.

The fan is designed to be wired direct to the mains supply

through a fused spur isolator (by others) and run continuously 

in the NORMAL mode (which is the low speed or trickle 

ventilation setting). The degree of extract from each room served

can be adjusted with the inlet grille balancing plates supplied.

(See page 2).

The unit is provided with adjustment for the trickle (low speed

or NORMAL) and high speed BOOST ventilation as standard.

The  NORMAL speed adjustment has a range of  0% to 50%. 

The unit is delivered with the NORMAL speed adjustment set to

0%. 

Note: the NORMAL speed must be set to 25% by the

installer.

An adjustment of 50 -100% is provided for the BOOST duty 

setting to reduce performance if necessary.

The unit is delivered with the BOOST speed adjustment set to

100%. (See the adjustments information on page 4).

Coding

MEV-B

Single fan unit.

MEV-2B

Twin fan unit (with auto duty sharing and standby).

MEV- B+

Dual fan unit (both fans continuous running). 

Duty

Units are available with one or two fans and with the following

free air duty:

100 l/s  (MEV-B  & MEV-2B).  

The MEV-B has a single fan and extracts 100 l/s.

The MEV-2B has two fans and extracts 100 l/s. The unit will

switch to the ‘standby’ fan in the event of a fan failure.

150 l/s  (MEV-B+). 

The MEV-B+ has two fans which run continuously and deliver 

150 l/s. In the event that one fan fails, the other will still deliver 

100 litres as a single fan until the unit is serviced. 

Typical mounting arrangements

The unit is designed for surface mounting onto a wall or ceiling.

Suggested layout arrangements with the fan serving multiple

rooms are shown on page 3.

Installation

IMPORTANT

The installation must be carried out by competent personnel

in accordance with the appropriate authority and conforming

to all statutory and governing regulations, ie IEE, COHSE, HVCA

etc.

Select a solid, non reverberant, mounting position (min. 50mm

clearance from any sidewall and min. 50mm from ceiling for

access to the top cover screw). The unit should be fitted with its

filters and any chosen inlet spigots. All necessary passages for

ductwork  from the rear outlet and any inlet spigots as well as

the electrical connections for the main unit and the remote

switch, should be prepared. 

It is assumed that compatible ductwork has been installed and

ready to be connected to the 125mm dia rear outlet (and any 

rectangular inlet spigot if fitted) of the unit.  

Note the unit is not fitted with a backdraught shutter. 

In continuous operation a backdraught shutter is not

required. 

Figure 1. General view of unit.

Wall tube and
fixed louvre grille
(by others).

Wall tube and
fixed louvre  
grille
(by others).

125 circular
ducting (by others)

Fan Ceiling Mounting

Fan Wall Mounting

Figure 2. Fan unit mounting arrangements.

The EMC Directive 
2004/108/EC  
The Low Voltage 
directive 
2006/95/EC

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: [email protected]  W: www.nuaire.co.uk

Содержание MEV-B

Страница 1: ...reduce performance if necessary The unit is delivered with the BOOST speed adjustment set to 100 See the adjustments information on page 4 Coding MEV B Single fan unit MEV 2B Twin fan unit with auto...

Страница 2: ...it casing Connect the ductwork to the outlet spigot and fix the unit to the surface Any subsidiary inlet ductwork can now be connected to the unit Fitting a subsidiary inlet spigot The subsidiary inle...

Страница 3: ...it grille T1 balancing plate fitted behind filter in separate water closet T1 Water Closet T1 T2 T2 Main room with additional utility room en suite bathroom and water closet T2 Bathroom T2 Water Close...

Страница 4: ...y to full speed 100 The performance of the unit can be reduced if required by rotating the screw anti clockwise Fully anti clockwise will give 50 of the available duty Adjusting the Low Speed normal t...

Страница 5: ...nit is totally isolated from the electrical supply This is particularly important when dealing with a run on circuit as input socket terminals within these units remain live even when the room light o...

Страница 6: ...considered Lifting gear such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken...

Страница 7: ...eded for dwellings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SA...

Страница 8: ...ts diffusers or to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequa...

Страница 9: ...ave all the fans been mounted and installed inline with the IEE wiring regulations Has the unit been installed in a position that will permit access for maintenance purposes Have all grilles or ductwo...

Страница 10: ...lectrical Connection Decision Yes No or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product...

Страница 11: ...s having a minimum equivalent area of 2 500mm are fitted in each room except wet rooms from which air is extracted Where this approach causes difficulties e g on a noisy site seek expert advice Have t...

Страница 12: ...dvice Decision Yes No or N A Has the customer been supplied with suitable documentation detailing maintenance and operational requirements Has the customer been advised not to seal natural air flows f...