11.0 FROST COIL INSTALLATION (OPTIONAL 

ANCILLARY) 

11.1 LPHW Frost Coil

LPHW frost coils are fitted with a frost stat on the air in side and an on/
off 230v valve actuator (Unit size 32 & 42 are NOT provided with valve 
and actuator). If the frosts stat switches to a frost condition, the valve 
actuator will open. The valve will open whether the fans are running 
or not. This is for pipe freeze protection. The LPHW section requires its 
own supply in order to power the valve actuator.

11.2 Wiring - LPHW Frost Coil Unit Sizes 07 - 42

External

Rotary 

Isolator

N

L1

LPHW Frost Heater Supply

(Overcurrent protection by others)

Recommended Frost 

Temperature Setting 4°C 

Heater Temperature

Setting

°C

-8

-2

2

8

46 

Wiring - LPHW Frost Coil 07 - 42

11.3 Electric Heater Frost Coil

Electric heater frost coils are fitted with its own internal control panel. 
The control is powered by a 400Vac 50Hz 3 phase & Neutral supply. 
This must be isolated local to the unit and fitted with appropriate 
overcurrent and fault protection. It connects to the main unit via “plug 
and play” interconnecting looms. (See interconnection section for 
details). No external connections are required. Electric heater elements 
are protected by a fail-safe over-temperature switch which will 
disconnect the heater supply if a temperature of 80°C is reached. Once 
the elements cool, the switch will reset but a power cycle is required to 
reset the heater supply contactor.

The frost coil is fitted with a burst fired controller with integral set 
point, air off thermistor, air in frost stat, thermal cut-out and contactor. 
The burst fired controller is only enabled if the frost stat reads a frost 
condition, the over-temperature cut-out is healthy AND a 24vac fan 
run signal is received from the main control panel. Once enabled the 
burst fired controller will increase heating output to achieve the set 
point set by the physical dial on the unit.

11.4 Wiring - Electric Heater Frost Coil Unit Sizes 07 - 22

 

External

Rotary 

Isolator

N

L1

Electric Heater 

Power Supply

L2

L3

Recommended Frost 

Temperature Setting 4°C 

Heater Temperature

Setting

°C

-8

-2

2

8

47 

Wiring - Electric Frost Coil 07 - 22

11.5 Wiring - Electric Heater Frost Coil Unit Sizes 32 - 42

External

Rotary 

Isolator

N

L1

Electric Heater 

Power Supply 1

L2

L3

External

Rotary 

Isolator

N

L1

Electric Heater 

Power Supply 2

L2

L3

Recommended Frost 

Temperature Setting 4°C 

Heater Temperature

Setting

°C

-8

-2

2

8

48 

Wiring - Electric Frost Coil 32 - 42

11.6 Electrical Supply FLC’s

‡ Double electric heater models require separate supplies for two 
heater sections, each with an appropriate overcurrent current 
protection device.

Unit Size

Electric Frost Heater 

FLC  (Anciliary)

LPHW Frost Coil FLC   

(Anciliary)

B*07V/**AT

17.5 A

0.1 A

B*07T/**AT

17.5 A

0.1 A

B*12V/**AT

35 A

0.1 A

B*12T/**AT

35 A

0.1 A

B*17V/**AT

52.5 A

0.1 A

B*17T/**AT

52.5 A

0.1 A

B*22V/**AT

52.5 A

0.1 A

B*22T/**AT

52.5 A

0.1 A

B*32V/**AT

52.5 A + 35 A ‡

0.1 A

B*32T/**AT

52.5 A + 35 A ‡

0.1 A

B*42V/**AT

52.5 A + 52.5 A ‡

0.1 A

B*42T/**AT

52.5 A + 52.5 A ‡

0.1 A

Содержание BPS V-AT

Страница 1: ...ufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel bu...

Страница 2: ...ce for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50mm double skinned panels and...

Страница 3: ...anded for Vertical PHX Units B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil...

Страница 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Страница 5: ...ndensate tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possib...

Страница 6: ...ht Hand Thermal Wheel Units SUPPLY SUPPLY CONTROLS Access 600mm Top View 14 Top View of Access For Right Hand Thermal Wheel Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exchanger Units Open Extra...

Страница 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Страница 8: ...ent must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed before the unit can be considered weather r...

Страница 9: ...t the requirement of removing the roof terminal Figure 21 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Страница 10: ...T 15 A 15 A 35 A 52 5 A 19 5 A 19 5 A 35 A 52 5 A B 42V AT 19 A 19 A 52 5 A 52 5 A 23 A 23 A 52 5 A 52 5 A B 42T AT 22 5 A 22 5 A 52 5 A 52 5 A 27 A 27 A 52 5 A 52 5 A Denotes any Character These heat...

Страница 11: ...ddress 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No Di AI DO AO Fresh Air Sensor 1 4 5 1 Supply Air Sensor 2 6 7 1 Return...

Страница 12: ...ocks 28 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 13: ...heating and Reverse Cycle DX cooling Section 7 10 10 7 10 1 Code Description B 8 17 T L R AT L 1 2 3 4 5 6 7 8 1 Range B Boxer Packaged Solution 2 ErP Compliance Year 6 2016 8 or No Affix 2018 3 Unit...

Страница 14: ...tion Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel Internal Connection are not shown for clarity 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Prot...

Страница 15: ...l 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Cu...

Страница 16: ...n S2 S3 Mitsubishi Electric PAC IF012B E Interface HX Bypass Relay Fan Run Relays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Volta...

Страница 17: ...ays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensatio...

Страница 18: ...ac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting...

Страница 19: ...minal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400...

Страница 20: ...ote1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotar...

Страница 21: ...Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandatory Customer Co...

Страница 22: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Страница 23: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Страница 24: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Страница 25: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Страница 26: ...e concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct senso...

Страница 27: ...drawings for details of the type of fan and drive that is fitted Maintenance guidelines for all fans are beyond this manual please contact Nuaire for specific documents Before any work is carried out...

Страница 28: ...Months Check filters and change clean if required failure to do so may impair the performance and energy efficiency of this unit Ensure condensate drains are cleaned clear and that water can flow fre...

Страница 29: ...cool the switch will reset but a power cycle is required to reset the heater supply contactor The frost coil is fitted with a burst fired controller with integral set point air off thermistor air in f...

Страница 30: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Страница 31: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Страница 32: ...32 01 09 21 Document Number 671746 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V AT Installation Manual NOTES...

Отзывы: