background image

27

01. 09. 21. Document Number  671746

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS V-AT

Installation Manual

All coils sit in a common drip tray connected to the pre-fitted 
condensate pump.

The coil panel has been pre-drilled and fitted with appropriate 
grommets for pipe connections. Do not drill or cut the unit casing for 
this purpose.

Coils should have their finned surface examined for accumulation of 
dirt, lint and biological contaminants or similar. If necessary, wash 
down affected areas with a mild detergent solution and a soft brush. 
Care should be taken not to damage the finned surface, and any 
cleaning fluids should be rinsed away with water.

A compressed air line may be used to blow out any solids between 
fins. Do not probe the coil fin block with metal objects as damage 
may cause leaks. Drain lines should be checked to ensure that they 
are unobstructed and free draining. Drain pans should be flushed out 
periodically to remove contamination.

The unit application may require particular attention to this item – 
Check with Building Management personnel for details.

9.6 Thermal Wheel

After the 2-3 weeks of operation, and at least once per year, ensure the 
following maintenance is performed.

Check that rotor is vertical and centred in casing. Adjust vertical 
and horizontal position if needed.

Check the thermal wheel spins freely.

Adjust sealing to ensure contact with the rotor and side plates. 
Replace brush sealing if it is worn.

Check that motor bracket is in 20-45° angle from horizontal line.

Adjust length of drive belt if needed.

Check condition of belt and belt lock (joint).

20-45°

45 

Thermal Wheel Belt

Experience shows that clogging of heat exchangers is not expected 
in normal cooling and air-conditioning systems. However, if deposits 
accumulate on the exchanger when used for special applications, it can 
be cleaned as follows:

Remove dust and fibres with a soft brush or vacuum cleaner. Use 
caution when blowing dirt out with compressed air to avoid damage to 
the wheel. Keep at a distance!

Oils, solvents etc. can be removed with hot water (max. 70 °C) or 
grease-removing solvents or immersion.

9.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

9.1 Fans

Please refer to general arrangement drawings for details of the type 
of fan and drive that is fitted. Maintenance guidelines for all fans are 
beyond this manual, please contact Nuaire for specific documents.

Before any work is carried out, please ensure that:

The power supply to the motor is switched off.

The fan impeller is at rest.

Measures are taken to ensure that the accidental, uncontrolled running 
of the fan is prevented during maintenance work.

In general, fans should be inspected twice a year, and care should be 
taken to ensure that any unusual vibration or sound is investigated as 
an urgent matter.

Access to the fan section is via hinged or lift-off panels. Cable entry 
must be made through the apertures provided. Screwed glands with 
cable restraint devices should be used.

9.2 General Fan Maintenance

Access to the fan is normally gained by opening the hinged access 
doors.

Care should be taken to remove any build up of dust (a light vacuum or 
light brushing will normally take care of this) Do not use a steam or any 
other high pressure cleaners.

Inspect the connection between the fan and unit for any damage or 
wear and tear.

9.3 Bearings

The bearings that are fitted will be (unless otherwise specified) “sealed 
for life”, therefore consequence maintenance is not required. 

Fan bearings are lifelong; up to 40,000 hours of operation. In cases of 
heavy duty operation, maintenance intervals are to be established by 
the operator.

9.4 Filters

When removing the filter access panels, pay attention to the airflow 
direction marked on the panel, this must be replaced to the exact 
position prior to being removed. Disposable filters should be checked, 
and changed when they become fully laden with dust. Washable filters 
should be removed and washed in a mild detergent, flushed with clean 
water and allowed to dry before refitting.

9.5 Coils

Coils should be connected to ensure that full counter flow exists i.e. the 
entering airflow meets the return connection.

All coils should be connected with the flow at the bottom and the 
return at the top unless otherwise advised. Drain and bleed valves are 
located on the coil, others may be required in the system pipe-work 
depending on the installation.

Frost protection must be incorporated on shut down and fresh air 
conditions to avoid coil freezing. Ideally, where the system is at risk of 
frost damage, the addition of a proprietary antifreeze solution to the 
water is recommended.

Pipe-work connections should be made to the unit using appropriate 
techniques, and must be independently supported. The connections 
should be pressure tested. 

Содержание BPS V-AT

Страница 1: ...ufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel bu...

Страница 2: ...ce for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50mm double skinned panels and...

Страница 3: ...anded for Vertical PHX Units B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil...

Страница 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Страница 5: ...ndensate tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possib...

Страница 6: ...ht Hand Thermal Wheel Units SUPPLY SUPPLY CONTROLS Access 600mm Top View 14 Top View of Access For Right Hand Thermal Wheel Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exchanger Units Open Extra...

Страница 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Страница 8: ...ent must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed before the unit can be considered weather r...

Страница 9: ...t the requirement of removing the roof terminal Figure 21 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Страница 10: ...T 15 A 15 A 35 A 52 5 A 19 5 A 19 5 A 35 A 52 5 A B 42V AT 19 A 19 A 52 5 A 52 5 A 23 A 23 A 52 5 A 52 5 A B 42T AT 22 5 A 22 5 A 52 5 A 52 5 A 27 A 27 A 52 5 A 52 5 A Denotes any Character These heat...

Страница 11: ...ddress 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No Di AI DO AO Fresh Air Sensor 1 4 5 1 Supply Air Sensor 2 6 7 1 Return...

Страница 12: ...ocks 28 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 13: ...heating and Reverse Cycle DX cooling Section 7 10 10 7 10 1 Code Description B 8 17 T L R AT L 1 2 3 4 5 6 7 8 1 Range B Boxer Packaged Solution 2 ErP Compliance Year 6 2016 8 or No Affix 2018 3 Unit...

Страница 14: ...tion Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel Internal Connection are not shown for clarity 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Prot...

Страница 15: ...l 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Cu...

Страница 16: ...n S2 S3 Mitsubishi Electric PAC IF012B E Interface HX Bypass Relay Fan Run Relays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Volta...

Страница 17: ...ays Controller Fuse 5A Condensate Pump Fuse 1A Aux Fuse 1A 24Vac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensatio...

Страница 18: ...ac Fuse 1 6A Lighting Thermal Wheel Terminal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting...

Страница 19: ...minal Extra Low Voltage SL Enable UI5 0 10V Room Temperature Sensor Optional Note1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400...

Страница 20: ...ote1 Anti Condensation Heater Thermostat Supply Fan Extract Fan Controller Lighting Thermal Wheel 0 24V 15V 0 15V 230V 400V 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotar...

Страница 21: ...Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 Key Factory Connection Customer Connection Mandatory Customer Co...

Страница 22: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Страница 23: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Страница 24: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Страница 25: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Страница 26: ...e concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct senso...

Страница 27: ...drawings for details of the type of fan and drive that is fitted Maintenance guidelines for all fans are beyond this manual please contact Nuaire for specific documents Before any work is carried out...

Страница 28: ...Months Check filters and change clean if required failure to do so may impair the performance and energy efficiency of this unit Ensure condensate drains are cleaned clear and that water can flow fre...

Страница 29: ...cool the switch will reset but a power cycle is required to reset the heater supply contactor The frost coil is fitted with a burst fired controller with integral set point air off thermistor air in f...

Страница 30: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Страница 31: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Страница 32: ...32 01 09 21 Document Number 671746 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS V AT Installation Manual NOTES...

Отзывы: