SG10050602

GENERAL INSTRUCTIONS

The SG100 & 170  burners are
supplied for On/Off or High/Low
operation and for use with single
phase electrical supply. Where an
instruction or information is
applicable to only one of the burner
types, single or two stage, then this
is indicated in the text.

This manual is structured to enable
the user to proceed from the delivery
of the burner to its commissioning
and use.

The conditions to be fulfilled and the
controls and adjustments to be used
are dealt with in the sequence that
should be followed for the correct
assembly installation and use.
Commissioning procedures are
described and the location of
necessary controls and adjustments
to undertake these runs are
illustrated and supported by
appropriate tabular matter and
graphs.

Routine Maintenance and Fault
Finding  complete the manual;
literature on proprietary components
is available on request.

SETTING COMBUSTION HEAD

The venturi flame ring assembly is
adjustable longitudinally so that the
restriction between the air diffuser
and the throat of the flame tube
effectively meters the combustion air
and therefore the assembly should
be set to approximately the position
corresponding to the required gas
rate.

Method of Adjustment

Undo the two safety bolts of the
hinged extension.

Remove one hinge pin on the
opposite side to that which it is
required to swing the burner.

Unplug any electrical connections
that are restricting movement.

Swing the burner body away slowly,
at the same time unclipping the
ignition and flame detector leads.

Undo the lock nut clamping bolt.

Lift out the venturi flame ring
assembly.

Undo the socket set screw.

Adjust the position of the assembly
in the socket of the supporting elbow
aligning the required scribed ring
against the end of the socket.

The positon is relative to the firing
rate of the burner, the graph below
shows the relation between the head
setting and burner output.

Secure the assembly and replace in
reverse order taking care that the
assembly sits squarely on the gas
inlet spigot and is squarely locked
in position by its clamping bolt, and
that the burner is swung back into
position the ignition and flame
detector leads are carefully clipped
back on their respective electrodes
(the terminal ends are dissimilar so
that they cannot be wrongly
connected).

BURNER AIR CONTROLS

The air for combustion is controlled
by an adjustable air flap located
inside the air inlet on the right hand
side of the burner viewed from the
rear.

Its purpose is to regulate and control
the volume of combustion air flowing
through the burner.
On all burners the air adjustment can
be made with or without the cover
fitted with the use of an Allen key.
There is a visible scale to assist in
the setting of combustion air, it is
numbered between 1 and 22.
Final fine adjustment must be made
with the cover on.

Air Diffuser

The air diffuser is fitted to the front
end of the inner assembly and
located within the flame tube.

It controls the volume of combustion
air and creates a pressure drop over
the burner head to ensure good fuel/
air mixing and flame stability.

Burner Output (kW)

H

e

a

d

 S

e

tt

in

g

He

ad

 S

ett

ing

SG100

C

h

a

m

b

e

R

e

s

is

ta

n

c

e

 (

m

b

a

r)

SG170

VENTURI HEAD SETTING

Содержание Selectos

Страница 1: ...Installation Maintenance Manual Series SG fully automatic gas burners Selectos SG100 SG170 Gas Burner 11 12 Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Страница 2: ...aught gas burner commissioning In the UK it is a legal requirement that anyone working on gas installation as defined in the Gas Safety Installation Use Regulations 1998 is CORGI registered The manufa...

Страница 3: ...irDamper 6 Air Pressure Switch 7 FanShield 8 FanWheel 9 Air Adjustment 10 FanMotor 11 ElectricalConnection 12 FlameTube 13 FlameProbe 14 IgnitionElectrode 15 Head Adjustment Screw 16 Pressure Test Poi...

Страница 4: ...192 60 275 113 139 114 ELECTRICALDATA Type Motor Ignition Transformer SG100 125W 2800rpm 230v 50Hz 0 65A Electronic 230 11000V SG170 125W 2800rpm 230v 50Hz 0 65A Electronic 230 11000V Type SG100 SG170...

Страница 5: ...unit refer to the manufacturers recommendations If the burner is to be used with an existing appliance preparethemountingflange Ensure the joint between appliance and burner is effectively sealed with...

Страница 6: ...ipping the ignition and flame detector leads Undo the lock nut clamping bolt Lift out the venturi flame ring assembly Undo the socket set screw Adjust the position of the assembly in the socket of the...

Страница 7: ...Burners The operating sequence begins with a pre purge on full air then start rate gas flame which when proved allows the burner to operate on main flame then to the OFF position after the heat input...

Страница 8: ...412 B07 Includes gas pressure governor safety two position main and pilot valves TWO STAGE ON OFF USING MAIN GAS IGNITION MULTIBLOC MB ZRDLE 405 412 B01 Includes gas pressure governor safety two main...

Страница 9: ...This low voltage protection works not only during start up but also permanently during operation LOCK OUTIDENTIFICATION InthecaseofafailuretheLEDispermanentlyilluminated Every10secondstheillumination...

Страница 10: ...d conduct the gas into atmosphere After purging the gas line re tighten the screw LEAKAGETESTING When making a leak test of the gas supply system the gas valve should beclosed Connectapressuregauge to...

Страница 11: ...e adjuster clockwise if a heavy light up is encountered Repeat until a satisfactory setting is achieved B07 VALVE The adjuster acts to control the rate of change between high and low position Turn the...

Страница 12: ...e power supply Replace UV cell switch on the power supply Reset lockout ROUTINE MAINTENANCE Switch off electrical supply and gas supply to the burner Combustion Air Fan Access can be gained to the com...

Страница 13: ...__________ Burner Type ___________ Size ___________ Serial No ___________ Commissioning date _________________________________ Guarantee Expiry date _______________________________ Gas type __________...

Страница 14: ...G10130501 BURNER SERVICE RECORD DATE DETAILS OF SERVICE SIGNATURE The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustmen...

Страница 15: ...G10130501 BURNER SERVICE RECORD DATE DETAILS OF SERVICE SIGNATURE The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustmen...

Страница 16: ...itch is in order otherwise the air pressure switch is faulty and must be renewed If the air pressure switch isn t in its made position the motor will start for approximately 2 to 3 seconds it then wil...

Страница 17: ...y There is sufficient gas The control box is not faulty Incorrect Rotation Of Burner Motor Motor rotates clockwise viewed from the shaft end If the burner motor rotation is incorrect the single phase...