BURNER GAS CONTROLS & ADJUSTMENTS

SINGLE STAGE (ON/OFF) USING PILOT GAS - MULTIBLOC MB-DLE 405-412 B07

Includes gas pressure governor, safety, main and start gas valves.

SINGLE STAGE (ON/OFF) MAIN GAS IGNITION - MULTIBLOC MB-DLE 405-412 B01

Contains gas pressure governor, safety, and main gas valves.

ADJUSTMENTS

A

Governor adjustment (main and pilot). Turn clockwise to increase
pressure. Range  4-20 mbar.

B

Start gas rate (B07 valve only). Turn anticlockwise to increase
and clockwise to decrease rate.

C

Main valve. Fast initial lift adjuster.

D

Main gas adjustment. Slacken cheesehead screw, and turn the
fluted knob anticlockwise to open, clockwise to close.

E

Low gas pressure switch (Optional).

F

Upstream testpoint.

G

Downstream testpoint.

TWO STAGE (HIGH/LOW) USING PILOT GAS - MULTBLOC MB-ZRDLE 405-412 B07

Includes gas pressure governor, safety, two position main and pilot valves.

TWO STAGE (ON/OFF) USING MAIN GAS IGNITION - MULTIBLOC MB-ZRDLE 405-412 B01

Includes gas pressure governor, safety, two main and start gas valves.

ADJUSTMENTS

A

Governor adjustment for main flame. Turn clockwise to increase
pressure. Range 3 - 20 mbar.

B

Start gas rate (B07 valve only). Turn anticlockwise to increase and
clockwise to decrease rate.

C

Main valve - first and second stage - fast initial lift adjuster.

D

High flame throughput adjustment. Slacken off locking screw, turn
anticlockwise to increase and clockwise to decrease rate.

E

Low flame throughput adjustment, as in D.

F

Low pressure gas switch (Optional).

G

Upstream testpoint.

H

Downstream testpoint.

GAS MULTIBLOCK SCHEMATIC

A

D

E

F

B

G

C

A

E

C

B

H

D

G

F

1

3

V1

V2

V3

5

2

4

V1 - Valve 1
V2 - Valve 2 - Single Stage (MB-D) or Two Stage(MB-Z)
V3 - Pilot Valve (B07 Only)
1 - Pressure Switch (Optional)
2 - Regulator
3 - Restrictor
4 - Filter
5 - Inlet connection

SG10070501

Содержание Selectos

Страница 1: ...Installation Maintenance Manual Series SG fully automatic gas burners Selectos SG100 SG170 Gas Burner 11 12 Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Страница 2: ...aught gas burner commissioning In the UK it is a legal requirement that anyone working on gas installation as defined in the Gas Safety Installation Use Regulations 1998 is CORGI registered The manufa...

Страница 3: ...irDamper 6 Air Pressure Switch 7 FanShield 8 FanWheel 9 Air Adjustment 10 FanMotor 11 ElectricalConnection 12 FlameTube 13 FlameProbe 14 IgnitionElectrode 15 Head Adjustment Screw 16 Pressure Test Poi...

Страница 4: ...192 60 275 113 139 114 ELECTRICALDATA Type Motor Ignition Transformer SG100 125W 2800rpm 230v 50Hz 0 65A Electronic 230 11000V SG170 125W 2800rpm 230v 50Hz 0 65A Electronic 230 11000V Type SG100 SG170...

Страница 5: ...unit refer to the manufacturers recommendations If the burner is to be used with an existing appliance preparethemountingflange Ensure the joint between appliance and burner is effectively sealed with...

Страница 6: ...ipping the ignition and flame detector leads Undo the lock nut clamping bolt Lift out the venturi flame ring assembly Undo the socket set screw Adjust the position of the assembly in the socket of the...

Страница 7: ...Burners The operating sequence begins with a pre purge on full air then start rate gas flame which when proved allows the burner to operate on main flame then to the OFF position after the heat input...

Страница 8: ...412 B07 Includes gas pressure governor safety two position main and pilot valves TWO STAGE ON OFF USING MAIN GAS IGNITION MULTIBLOC MB ZRDLE 405 412 B01 Includes gas pressure governor safety two main...

Страница 9: ...This low voltage protection works not only during start up but also permanently during operation LOCK OUTIDENTIFICATION InthecaseofafailuretheLEDispermanentlyilluminated Every10secondstheillumination...

Страница 10: ...d conduct the gas into atmosphere After purging the gas line re tighten the screw LEAKAGETESTING When making a leak test of the gas supply system the gas valve should beclosed Connectapressuregauge to...

Страница 11: ...e adjuster clockwise if a heavy light up is encountered Repeat until a satisfactory setting is achieved B07 VALVE The adjuster acts to control the rate of change between high and low position Turn the...

Страница 12: ...e power supply Replace UV cell switch on the power supply Reset lockout ROUTINE MAINTENANCE Switch off electrical supply and gas supply to the burner Combustion Air Fan Access can be gained to the com...

Страница 13: ...__________ Burner Type ___________ Size ___________ Serial No ___________ Commissioning date _________________________________ Guarantee Expiry date _______________________________ Gas type __________...

Страница 14: ...G10130501 BURNER SERVICE RECORD DATE DETAILS OF SERVICE SIGNATURE The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustmen...

Страница 15: ...G10130501 BURNER SERVICE RECORD DATE DETAILS OF SERVICE SIGNATURE The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustmen...

Страница 16: ...itch is in order otherwise the air pressure switch is faulty and must be renewed If the air pressure switch isn t in its made position the motor will start for approximately 2 to 3 seconds it then wil...

Страница 17: ...y There is sufficient gas The control box is not faulty Incorrect Rotation Of Burner Motor Motor rotates clockwise viewed from the shaft end If the burner motor rotation is incorrect the single phase...

Страница 18: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Отзывы: