If the hinged extension/flame tube assembly is not fitted to
the fan case assembly, it should be fitted before mounting to
the application using the pins provided. Ensure that the gas
inlet connection is at the bottom.
Once the burner is mounted open the hinged extension,
connect the flame probe and ignition cables. The terminal
ends are dissimilar and cannot be wrongly connected.

The gas train can now be fitted to the hinged extension.

Ensure that the gaskets are seated correctly when
tightening the assembly.

If the burner is to be fitted to a new packaged unit, refer
to the manufacturers recommendations.

If the burner is to be used with an existing appliance
prepare the mounting flange.

Ensure the joint between appliance and burner is
effectively sealed with the gasket provided.

140-190

15

5-

21

P

C

D

12

D

ia

1

3

.0

m

m

2

 P

L

A

C

E

S

12

.0

m

m

4 P

LA

C

E

S

MOUNTING THE BURNER

ELECTRICAL

EXTERNAL WIRING

ADDITIONAL CONNECTIONS FOR 

HIGH/LOW VALVES

7 PIN BLACK/BROWN

WIELAND PLUG

4 PIN BROWN

WIELAND PLUG

ON/OFF VALVES

ELECTRICAL POWER SUPPLY

Connect a single phase 50Hz electrical supply to the burner observing all applicable IEE Regulations. Refer to the
connection diagram below or the wiring diagram contained in the instruction pack supplied with the burner.

ELECTRICAL CONNECTIONS

MOUNTING FLANGE DETAIL

Содержание Selectos

Страница 1: ...Installation Maintenance Manual Series SG fully automatic gas burners Selectos SG100 SG170 Gas Burner 11 12 Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Страница 2: ...aught gas burner commissioning In the UK it is a legal requirement that anyone working on gas installation as defined in the Gas Safety Installation Use Regulations 1998 is CORGI registered The manufa...

Страница 3: ...irDamper 6 Air Pressure Switch 7 FanShield 8 FanWheel 9 Air Adjustment 10 FanMotor 11 ElectricalConnection 12 FlameTube 13 FlameProbe 14 IgnitionElectrode 15 Head Adjustment Screw 16 Pressure Test Poi...

Страница 4: ...192 60 275 113 139 114 ELECTRICALDATA Type Motor Ignition Transformer SG100 125W 2800rpm 230v 50Hz 0 65A Electronic 230 11000V SG170 125W 2800rpm 230v 50Hz 0 65A Electronic 230 11000V Type SG100 SG170...

Страница 5: ...unit refer to the manufacturers recommendations If the burner is to be used with an existing appliance preparethemountingflange Ensure the joint between appliance and burner is effectively sealed with...

Страница 6: ...ipping the ignition and flame detector leads Undo the lock nut clamping bolt Lift out the venturi flame ring assembly Undo the socket set screw Adjust the position of the assembly in the socket of the...

Страница 7: ...Burners The operating sequence begins with a pre purge on full air then start rate gas flame which when proved allows the burner to operate on main flame then to the OFF position after the heat input...

Страница 8: ...412 B07 Includes gas pressure governor safety two position main and pilot valves TWO STAGE ON OFF USING MAIN GAS IGNITION MULTIBLOC MB ZRDLE 405 412 B01 Includes gas pressure governor safety two main...

Страница 9: ...This low voltage protection works not only during start up but also permanently during operation LOCK OUTIDENTIFICATION InthecaseofafailuretheLEDispermanentlyilluminated Every10secondstheillumination...

Страница 10: ...d conduct the gas into atmosphere After purging the gas line re tighten the screw LEAKAGETESTING When making a leak test of the gas supply system the gas valve should beclosed Connectapressuregauge to...

Страница 11: ...e adjuster clockwise if a heavy light up is encountered Repeat until a satisfactory setting is achieved B07 VALVE The adjuster acts to control the rate of change between high and low position Turn the...

Страница 12: ...e power supply Replace UV cell switch on the power supply Reset lockout ROUTINE MAINTENANCE Switch off electrical supply and gas supply to the burner Combustion Air Fan Access can be gained to the com...

Страница 13: ...__________ Burner Type ___________ Size ___________ Serial No ___________ Commissioning date _________________________________ Guarantee Expiry date _______________________________ Gas type __________...

Страница 14: ...G10130501 BURNER SERVICE RECORD DATE DETAILS OF SERVICE SIGNATURE The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustmen...

Страница 15: ...G10130501 BURNER SERVICE RECORD DATE DETAILS OF SERVICE SIGNATURE The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustmen...

Страница 16: ...itch is in order otherwise the air pressure switch is faulty and must be renewed If the air pressure switch isn t in its made position the motor will start for approximately 2 to 3 seconds it then wil...

Страница 17: ...y There is sufficient gas The control box is not faulty Incorrect Rotation Of Burner Motor Motor rotates clockwise viewed from the shaft end If the burner motor rotation is incorrect the single phase...

Страница 18: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Отзывы: