Page 29
NDFL100-38 / BR003211 / Rev. 220900A
Flame failure in changing to high flame - Oil
firing Only
(or small sparky high flame).
High flame nozzle blocked / excess air
condition.
Burner fails change to low flame - Oil firing
only
(except on initial start).
Check setting and operation of high/low
control instrument.
Burner locks out without attempting to light
If the UV/photocell detects light before the pre-
purge period, the burner will lockout, the cause
will be extraneous light.
S
PARE
P
ARTS
For spare parts contact Nu-ways Parts and Com-
ponents Division at the address and telephone
number listed on the rear cover of this handbook.
To avoid delays, please provide the burner model
and specification number.