background image

NDFL100-38  /  BR003211  /  Rev. 220900A

Page  22

One quick press of the PGM button, the display

changes  to  show  the  set  point  as  the  larger  red

digits and the SPI in the lower small green digits.
Alter the red display using the up/down buttons to

show the new required set point, press exit or let

the  unit  time  out  to  return  to  the  basic  display

which should be the new set point figure.

To enter a new parameter

The parameters dictate the way in which the burner

firing  rate  alters  in  response  to  changes  in  the

pressure/temperature of the boiler.
A major factor that determines the need to change

the parameters is if the burner is fitted to a steam

or hot water boiler.  The table below indicates the

parameter and it’s setting for steam and hot water

boilers.  It must be emphasised that it is only an

indication and any departure from these settings

should  be  made  in  small  increments,  with  time

given  to  see  how  the  burner  is  reacting  to  the

changed parameter.
Press  and  hold  the  PGM  button  down  until  the

green set point figure changes to an AL, the larger

upper figures show the value.  Use the up/down

buttons to set the new value, press the PGM button

to enter the value and change to the next screen.

To cancel an entry press exit.  Scroll through the

screens, (PGM button) modifying any value found

to be in error (up/down buttons).  At the last screen

the PGM button will return the controller to the

original operating display.
At any point in the procedure the original operating

display  can  be  obtained  by  letting  the  unit  time

out, the value in the display at the time out will be

accepted.
A value can only be altered within the permitted

range of that parameter. All other parametrs must

remain as supplied.
Note: The detector range parameters SCL & SCH

are given as °C for Hot Water (temperature) and

bar for Steam (pressure).

NDFL - O

IL

O

PERATION

There are three atomising nozzles. The top nozzle

only sprays on low flame whilst two spray together

for  the  intermediate  flame  and  all  nozzles  spray

on high flame. The oil operating pressure is 300

psi.

5:)

5

(&200(1'('

6

(77,1*6

3DUDPHWHU

'LVSOD\

+RW

:DWHU

6WHDP

3URSRUWLRQDO

EDQG

3E

'HULYDWLYH

WLPH

'W

5HVHWWLPH

5W

$FWXDWRU

WLPH

7W

6HWWRWKH$LU

'DPSHUUXQQLQJ

WLPHEHWZHHQORZ

 KLJKIODPH

6ZLWFKRQ

WKUHVKROG

+\V

8SSHURII

WKUHVKROG

+\VW

'HWHFWRU

UDQJHVWDUW

6&/

'HWHFWRU

UDQJHHQG

6&+

At the start of the firing cycle, there is a pre-purge

with  forced  air  and  ignition.  At  the  end  of  this

period, the air damper moves from the high fire

position to the ignition position. After a delay, the

low flame and safety (if fitted) solenoid valves are

energised, allowing oil to flow. The burner will light,

and the ignition is switched off. After a stabilising

period,  the  air  damper  moves  to  the  low  fire

position. If the flame fails to establish the burner

will go to lockout. If there is flame failure during

operation, the burner will shut down, and a single

restart cycle will follow.

Three-Nozzle System

When the air damper moves to the next pre-set

positions,  the  nozzle  control  valves  open  in

sequence. The burner will be held in any of the

three  positions  under  the  control  of  the  boiler

thermostats.

C

OMMISSIONING

 

THE

  B

URNER

Check  that  the  electrical  wiring  is  complete  and

complies with all applicable Codes and Standards.
Check that the fuses are fitted and correctly sized.

Содержание NDFL100-38

Страница 1: ...Page 1 NDFL100 38 BR003211 Rev 220900A HANDBOOK Model NDFL100 38 fully automatic dual fuel burner MPA22 RWF40 Worcester Hospital Contract BR003211 Natural Gas Class D Oil...

Страница 2: ...s Supply 15 Fuel Oil Storage and Handling 15 Fuel Oil Supply 15 Gravity feed system 15 Suction lift System 15 Flue and Chimney Requirements 15 Plant Room Ventilation 16 Existing Appliances 16 Combusti...

Страница 3: ...TAEFA MODULATION CONTROLLER TYPE RWF 40 21 Basic display 21 To change the working set point 21 To enter a new parameter 22 NDFL OIL 22 OPERATION 22 Three Nozzle System 22 COMMISSIONING THE BURNER 22 E...

Страница 4: ...ED until such time that the fault has been investigated and rectified EUROPEAN BOILER EFFICIENCY DIRECTIVE B E D All burners and boiler bodies marketed seperately within the European Union must comply...

Страница 5: ...Q L Q G R Z 2 L O H H G 2 L O 5 H W X U Q L U 3 U H V V X U H 6 Z L W F K D V 6 R O H Q R L G 9 D O Y H D V 3 U H V V X U H 6 Z L W F K R P E L Q H G D V 6 R O H Q R L G 9 D O Y H R Y H U Q R U O D P...

Страница 6: ...TAILS DV 6SLNH DV QQHU VVHPEO 2LO QQHU VVHPEO 2LO 1R OH ORFN 2LO 9DOYH 0DQLIROG DV QWU JQ OHFWURGH DV JQ OHFWURGHV 2LO LQJHG WHQVLRQ DV 1R OH ODPH 7 XEH LIIXVHU RZ ODPH 2LO 1R OH LJK ODPH 2LO 1R OHV 2...

Страница 7: ...HVFULSWLRQ 03 LVSOD DV XUQHU 2Q 2II 6ZLWFK 5 0RGXODWLQJ RQWURO 0 LOWHUV 03 LVSOD 2LO 5HOD V XHO 6HOHFWRU 6ZLWFK 03 RQWURO DV DV QGLFDWRU DPS 03 RQWURO 2LO 2LO QGLFDWRU DPS XUQHU DQ 6WDUWHU XUQHU 2Q Q...

Страница 8: ...IS A SPECIAL COPY ISSUED TO ON IT WILL NOT BE KEPT UP TO DATE AND SHOULD BE RETURNED TO NU WAY DRAWING OFFICE NU WAY LIMITED P O BOX 1 VINES LANE DROITWICH WORCESTERSHIRE WR9 8NA ENGLAND TELEPHONE 01...

Страница 9: ...18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 conditions of use see page 1 for NU WAY LTD VINES LANE DROITWICH ENGLAND OF PAGE ISSUE DRAWING No 0 2 7 L1 L3 L2 INCOMING SUPPLY 400 3 50 CONTACTOR AND MO...

Страница 10: ...0723 L1 TE N G CG G D2 M9 CB CA D1 GND B9 M6 XU6 XB6 M1 I1 G1 X1 Q63 Q64 X1 Q14 Q13 Q Y1 Y2 8 9 U1 7 6 QAE22 AOTC INTERLOCK IF NOT REQ D LINK 6 7 INTERLOCK GAS BOOSTER TEMPERATURE DETECTOR BURNER FAUL...

Страница 11: ...3 4 5 6 2 12 3 4 2 11 23 24 7 7 PAGE 6 L1 E N CONTROL STAT LIMIT STAT T T F1 12 10 11 13 PAGE 5 ISOLATING VALVE MICROSWITCHES IS CLOSED CLOSED WHEN VALVE 9 5 6 15 10 6 6 14 10 2 9 1 10 6 6 23 9 1 6 18...

Страница 12: ...4 3 2 1 WE 0723 8 9 6 7 4 5 2 3 1 18 16 17 14 15 12 13 10 11 31 30 29 28 27 26 25 24 23 22 21 20 19 P AIR PRESSURE SWITCH ACTUATOR GAS FLAP GAS IGNITION TRANSFORMER P ACTUATOR GAS FLAP GAS PRESSURE SW...

Страница 13: ...ISSUE 0 PAGE 7 6 OF WE 0723 ACTUATOR AIR FLAP DISPLAY B4 T2 S3 N T1 E L1 T8 PE CELL CLK B5 T7 T6 9 8 7 5 6 4 3 1 2 TXD G5V RXD DIR IN OUT GND P E CELL ACTUATOR AIR FLAP DISPLAY PAGE 4 PAGE 4 T T 3 STA...

Страница 14: ...ES LANE DROITWICH ENGLAND DRAWING No ISSUE 0 OF 7 7 KM1 WE 0723 TRANSFORMER OIL IGNITION OIL VALVE V3 OIL VALVE V2 GND DB DA FB FA 30 31 28 29 26 27 24 25 22 23 20 21 19 18 17 16 15 14 10 13 12 11 8 9...

Страница 15: ...ain to allow the burner to be isolated for maintenance To avoid any restriction in gas flow the size of this valve should not be less than that of the gas train Fuel Oil Storage and Handling The requi...

Страница 16: ...ure the joint between appliance and burner is effectively sealed with the gasket provided Unless otherwise specified the flame tube should be flush with the inner face of the appliance combustion cham...

Страница 17: ...it The system has many functions several of them need a pass code before the user can obtain access to them Entering this code is described in the following text When using the keys on the display un...

Страница 18: ...QIRUPDWLRQ PRGH LV DFWLYH FNQRZOHGJH PHQW H H FWXDWLRQ RI JDV IORZ FRQWURO IODS LQ FRQMXQFWLRQ ZLWK EXWWRQV H FWXDWLRQ RI DLU IORZ FRQWURO IODS LQ FRQMXQFWLRQ ZLWK EXWWRQV H H Q FRQMXQFWLRQ ZLWK EXWWR...

Страница 19: ...t be competed The procedure consists of the following Entering the pass code Reviewing the air and gas set points Firing the burner Commissioning the burner Completing the procedure Refer to page 17 f...

Страница 20: ...GAS EL display and start the burner Move to point P2 the firing rate will increase Adjust the air damper to give the correct combustion analysis Repeat the above procedure for points P3 through P8 fi...

Страница 21: ...s are properly secured Check that the appliance control instruments are set to safe limits On modulation burner check and set the RWF 40 3 0 7 6 0 16 DQGLV 6WDHID 5 XUQHU HQDEOH 5HGXFH RXWSXW QFUHDVH...

Страница 22: ...the display at the time out will be accepted A value can only be altered within the permitted range of that parameter All other parametrs must remain as supplied Note The detector range parameters SC...

Страница 23: ...oning the burner Completing the procedure Refer to page 18 for a functional description of the display unit Enter the pass code Initial Settings Air Damper 6HW 3RLQW 9DOXH HVFULSWLRQ 3 LJK ILUH DLU GD...

Страница 24: ...he burner will operate at the initial high flame position whilst adjusting either Make the adjustment with the 2 either the or keys Whilst in the high fire position check and set the firing rate Retur...

Страница 25: ...een and finally back to the operating display with each press of the acknowledgement key 6FUHHQ QIRUPDWLRQ DV 7RWDO FXELF PHWHUV RI IXHO FRQVXPHG 7RWDO KRXUV RI RSHUDWLRQ 1XPEHU RI VXFFHVVIXO VWDUWV 7...

Страница 26: ...ROOHU DGGUHVV 0RWRU VSHHG 0RWRU URWDWLRQ DQG UHIHUHQFH 6FUHHQ QIRUPDWLRQ 2LO LU VHWWLQJ SRLQW 3 LU VHWWLQJ SRLQW 3 KDQJHRYHU SRLQW 3 LU VHWWLQJ SRLQW 3 KDQJHRYHU SRLQW 3 LU VHWWLQJ SRLQW 3 0RVW UHFHQW...

Страница 27: ...ar solvent Replace fil ter and pump endplate A filter should be fitted in the fuel supply pipe If fitted with a disposable element this should be replaced at least once per year If the filter has a re...

Страница 28: ...only Whether the nozzle is spraying oil If not check that there is an oil supply to the burner and that all isolating valves are open That nozzle is not blocked and that atomisa tion is correct That...

Страница 29: ...k setting and operation of high low control instrument Burner locks out without attempting to light If the UV photocell detects light before the pre purge period the burner will lockout the cause will...

Страница 30: ...SH 6L H 6HULDO 1R XUQHU 7 SH 1 6L H 6HULDO 1R RPPLVVLRQLQJ DWH 6SHF Q 1R 6 XDUDQWHH SLU DWH DV 7 SH 1DWXUDO DV DV 3UHVVXUH XSVWUHDP RI WKH PDLQ JDV JRYHUQRU 6WDQGLQJ PEDU 5XQQLQJ PEDU 6HW SRLQW 3 3 3...

Страница 31: ...WHPS PELHQW WHPS 1HWW IOXH JDV WHPS IILFLHQF 200 66 21 1 6 7 66 2 7KH GHWDLOV EHORZ DUH WR EH FRPSOHWHG E WKH RPPLVVLRQLQJ QJLQHHU QVWDOOHUV 1DPH GGUHVV 6LWH GGUHVV SSOLDQFH 7 SH 6L H 6HULDO 1R XUQHU...

Страница 32: ...03211 Rev 220900A Page 32 BURNER SERVICE RECORD 7KH GHWDLOV EHORZ DUH WR EH FRPSOHWHG E WKH 6HUYLFLQJ QJLQHHU 7KLV VKHHW WR EH FRPSOHWHG DQG VLJQHG IROORZLQJ HDFK VHUYLFH DGMXVWPHQW DWH HWDLOV 2I 6HUY...

Страница 33: ...e 33 NDFL100 38 BR003211 Rev 220900A 7KH GHWDLOV EHORZ DUH WR EH FRPSOHWHG E WKH 6HUYLFLQJ QJLQHHU 7KLV VKHHW WR EH FRPSOHWHG DQG VLJQHG IROORZLQJ HDFK VHUYLFH DGMXVWPHQW DWH HWDLOV 2I 6HUYLFH 6LJQDWX...

Страница 34: ...NDFL100 38 BR003211 Rev 220900A Page 34 NOTES...

Страница 35: ...Page 35 NDFL100 38 BR003211 Rev 220900A...

Страница 36: ...Page 36 NDFL100 38 BR003211 PM65 NU WAY LIMITED P O Box 1 Vines Lane Droitwich Worc WR9 8NA England Telephone 01905 794331 e mail info nu way co uk Fax Office 01905 794017 Parts Components 01905 79582...

Отзывы: