background image

DELAYED IGNITION, BURNERS STARTS VIOLENTLY

BURNER FAILS TO START AFTER NORMAL OPERATION

Remedies

Situation

Possible causes

BURNER FAILS TO START

Check ignition transformer. Check electrode

gap and porecelains

Reset overheat device. Find reason for its

operation and rectify

Check or replace fuse if necessary. Check

reason for failure

Check operation of magnetic valve

Check that photo cell is not seeing ambient light

Motor runs

Flame instabillity

Burner pre-purges

Burner locks out

Motor runs

Photo cell failed

Control faulty

Confirm with new photo cell

Confirm with new control. (NB. it is advisable to

change the photo cell if also changing control)

Burner pre-purges

Burner locks out

No oil

Check that H.T. leads are sound and are not

arcing other than at electrode gap

No flame occurs

Check oil supply to burner - check that pump

is not airlocked

Burner fails to start

Lamp not lit

Fuse has blown

Appliance thermostat has not reset

Appliance overheat device has operated

Control relay or Photo cell defective

Adjust thermostat

Check by replacement

Motor runs

Burner runs to lockout

No oil being delivered

Excessive flue draught is preventing

flame establishment

No spark

Check that tank, oil lines, fire valve, pump and

nozzle are all in good order

Rectify condition

Excessive draught

Recommission burner

Burner pulsates-on start-up

Nozzle partly blocked

Oil pressure too low

Flue blocked or damaged

Fan slipping on shaft

Pump coupling loose or worn

Replace nozzle

Check and recommission

Check and rectify

Check and retighten

Delayed ignition

Check the electrode adjustment, see diagram

Check electrodes for damage

Check H.T. leads for damage and disconnection

Check and replace

Incorrect head settings

Low oil pressure

Photo cell not seeing light

Excess air

Burner pulsates on start-up

only with hot flue

Burner starts violently

False light

No spark

Check oil pressure

Check that photo cell is clean and unobstructed

Check nozzle to burner head dimension and

elektrode position

Adjust air damper

Flame occurs

171 915 01  91-06

FAULT LOCATION

Содержание MOL 1650-3R B70 2-3

Страница 1: ...Installation Maintenance Manual MOL 1650 3R B70 2 3 Oil Burner 11 12 Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Страница 2: ...udeddisc 3 Nozzle 4 Nozzle assembly 5 Ignitionelectrodes 6 Ignitioncable 7 Ignitiontransformer 8 Photocell 9 Controlbox 10 Relay base 11 Dampermotor 12 Indicating lamp Stage 3 13 Cover inspectionglass...

Страница 3: ...dthespray patternchangewiththepumppressure state a definite spray angle or spray pattern Lengthof Flange burner tube Measure B BurnerheadStandard 364 324 BurnerheadLongdesign 664 624 OUTPUTRANGEANDNOZ...

Страница 4: ...TECHNICAL DATA DIMENSIONS OF FLANGE 171 225 77 00 01 14 310 324 380 205 5...

Страница 5: ...Increase the nozzle assembly adjustment somewhat The CO2 con tent and consequently the air volume will then be reduced CONDENSATION IN CHIMNEY A modern burner works with less ex cess air and often al...

Страница 6: ...rds90 Adjust the operating switch back to stage 1 and check Stage 2 Adjust the operating switch to stage 1 I Reduce the air volume Turnorangecamtowards0 Increase the air volume Turnorangecamtowards90...

Страница 7: ...ower at the main switch and cut off the oil supply 171 305 93 01 01 NOTE For maintenance of the brake plate nozzles electrodes etc when using a long design of the burner tube you havetoremovethenozzle...

Страница 8: ...Operating switch Stage 3 S9 Control thermostat Stage 3 S20 Main switch T1 Ignitiontransformer X1 Connectionterminalboard X2 Earthterminal X3 Plug in contact Euro burner X4 Plug in contact Euro boiler...

Страница 9: ...r volume 22 s Safety time 5 s Post ignition time 15 s IntervalbetweenMv1andMv2 7 5 s Reset after lock out Immediately Time of re start 47 s Ambienttemperature 20 to 60 C Min required current at 220 V...

Страница 10: ...sumoftheseindividualresistances is so insignificant that they can be disregarded The tables do not include any lengths exceeding 100 m as experience shows that longer lengths are not needed Thetablesa...

Страница 11: ...so that there is a free passage back to the suction side through the return line with the return port closed EXCHANGE OF FILTER 171 505 39 94 02 One pipe system FUNCTION DANFOSS RSA 95 125 When the pu...

Страница 12: ...ge 1 2 Nozzle Stage 2 3 Nozzle Stage 3 4 Solenoid valve Stage 1 5 Solenoid valve Stage 2 6 Solenoid valve Stage 3 and adjustment device nozzle assembly 7 Oilpump 8 Adjustment device nozzle assembly 9...

Страница 13: ...255 219 22 43 266 229 23 34 277 238 24 23 287 247 25 07 297 256 25 91 307 264 26 70 317 272 6 00 22 34 265 228 23 42 278 239 24 47 290 250 25 46 302 260 26 43 313 270 27 49 326 280 28 27 335 288 29 1...

Страница 14: ......

Страница 15: ...not reset Appliance overheat device has operated Control relay or Photo cell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue d...

Страница 16: ...NOTES...

Страница 17: ...NOTES...

Страница 18: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Отзывы: