MGN 2800N HP 26
BURNER PERFORMANCE CURVE
Below is the detailed operating data for the MGN 2800N HP.
The graph contains the following:
The certified burner performance envelope
The gas head pressure curve
The combustion air head pressure curve
Gas train inlet pressure curves
The total minimum gas supply pressure is obtained by summing the combustion chamber resistance
and combined burner head and line loss (shown as solid lines). A further 2.5 mbar should be added
to allow for manufacturing tolerances, etc.
The gas and combustion air head pressure curves are supplied as a guide only and are not intended
to replace a full burner commissioning procedure using certified test equipment.
The burner outputs are based on the gross calorific value of natural gas (38.56 MJ/m
3
).
Содержание MGN 2800N
Страница 1: ...MGN 2800N Gas Burner Installation Maintenance Manual...
Страница 5: ...MGN 2800N HP 4 BURNER COMPONENT IDENTIFICATION 1 8 15 4 6 17 13 2 3 16 7...