5. - INSTALLATION REQUIREMENTS

  (FENTON CF) 

THIS APPLIANCE MUST BE INSTALLED AND SERVICED BY A PROPERLY QUALIFIED, (IN ACCORDANCE WITH LOCAL &  
NATIONAL CODES), INSTALLATION ENGINEER.   

 

It is the Law in the UK that All gas appliances are installed by a competent person in accordance with the GAS SAFETY (INSTALLATION 
AND USE) REGULATIONS 1998 (As amended), the relevant British Standards for Installation work, Building  
Regulations, Codes of Practice and these Instructions. In the UK a Registered Installer is deemed competent. In the  
Republic of Ireland, all Irish Standards, Local Codes and Bord Gais recommendations should be adhered to.  
The Installation should also be carried out in accordance with the following where relevant: 
1. BS5871 Part 2        2. BS5440 Parts 1 & 2        3. BS6461 Parts 1 & 2         4. BS6891        5. BS8303 
Building Regulations and Standards issued as relevant by the Department of the Environment or the Scottish Development  
Department. 

 

In the Republic of Ireland Installation should be carried out in accordance with IS813, ICP3, IS327, Building Regulations, Codes of  
Practice, these Manufacturers Instructions and any Rules In Force. 
Particular Reference should be made to the Ventilation Requirements, for the UK this Appliance would not normally require any  
additional purpose provided ventilation, for the Republic of Ireland ventilation should be in accordance with IS813 Domestic Gas  
Installations.            
Failure to comply with the above could leave the Installer Liable to Prosecution and Invalidate the Warranty. 

 

IMPORTANT

 

BEFORE PROCEEDING WITH THE INSTALLATION READ THESE INSTRUCTIONS CAREFULLY.  THESE INSTRUCTIONS SHOULD 

BE LEFT WITH THE USER FOR SAFE KEEPING AND FUTURE SERVICING.  PRIOR TO INSTALLATION ENSURE THAT THE GAS 

TYPE AND PRESSURE ARE AS STATED ON THE APPLIANCE DATA BADGE. 

 
 

6. - APPLIANCE DATA

  

a.

  Gas Type: See Data Plate, (Natural Gas at 20mbar or Propane at 37mbar). 

b. 

Burner Pressure:  Natural Gas 16.9mbar (Thermotronic & High Level Controls) 19.0mbar (Manual Control) cold. 

                                :  Propane 36.6mbar cold.

 

c.

  Control System: Manual or Thermatronic (Fully Sequential) Control System operated by Handset pointed at Receiver. 

d.

  Fire Safety: Oxygen Depletion & Flame Failure Device. 

e.

  Ignition: Manual-Integral Piezo Igniter, Thermatronic-Full Sequential Control. 

f.

  Inlet Connection: 8mm Compression Fitting to Gas Isolation Elbow. 

g.

  Category: I2H, I3P. 

h.

  Injector: Natural Gas (G20)- 310 Multi hole.    Propane (G31) - 160 Single hole. 

i.

  Heat Input: High: Natural Gas (G20) - 5.0kW Gross (4.5kW Nett)    Propane (G31) - 4.73kW Gross (4.35kW Nett) 

j.

  Heat Input: Low: Natural Gas (G20) - 2.8kW Gross (2.5kW Nett)    Propane (G31) - 2.7kW Gross (2.5kW Nett)  

k.

  Efficiency Class: 1.  The Efficiency of this appliance has been measured as specified in BS7977-1:2009 + A1 2013 and the results 

      obtained were Natural Gas 76.5% gross (84.9% Nett) and Propane 78.7% gross (85.6% Nett). The test data has been certified by BSI 
     Group (0086) and can be used in the UK Government’s Standard Assessment Procedure (SAP) for Energy Rating of Dwellings.        

l.

  Heat Output: High: Natural Gas (G20) - 3.82kW    Propane (G31) - 3.72kW 

m.

  Heat Output: Low: Natural Gas (G20) - 1.73kW    Propane (G31) - 1.75kW 

n.

  Pilot ODS Type: Natural Gas (G20) - P448D.  Propane (G31) - P449. 

o.  

Nitrous Oxide (NOx) -  130mg/kWh.

 

 

7. - APPLIANCE DIMENSIONS  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

FENTON CF DIMENSIONS 

552 

226 

625 

258 

627 

100 

120 

 15 

 57 

 
                                                                                 The diagram above shows the important dimensions only. 

Содержание FENTON CF

Страница 1: ...t not be placed close to or on the fire We recommend that a Fireguard conforming to BS8423 should be used for protection of Young Children the Elderly Infirm and Pets ALL INSTRUCTIONS MUST BE LEFT WIT...

Страница 2: ...Declaration of Conformity 32 22 Diagram of Thermatronic Radio Frequency Control System 33 Guarantee 34 BOX CONTENTS The Fire comes in a number of boxes Box 1 Large box contains the Fire the Matrix Tr...

Страница 3: ...bove 2 No6 x 5mm blunt self tapping screws for fixing the Case 1 10mm Back Nut olive to connect 8mm copper pipe gas supply to the burner via the isolation elbow 1 2 1 metre length of 6mm x 4mm self ad...

Страница 4: ...is the appliance must be serviced q Coal Wood Effect Parts are manufactured from RCF Refractory Ceramic Fibre are supplied with this appliance see Health Safety guidance Do not use real coals or wood...

Страница 5: ...mmand has been received and the push button should immediately be released to allow the control to operate Using the Thermatronic Remote Control System Control can only be achieved if the Handset is p...

Страница 6: ...e Small Flame button to set the Minute Press Off or simply wait to return to the manual screen IMPORTANT For the following modes of controlling the fire automatically for Temperature or Timer Programs...

Страница 7: ...ty alkaline e To change the Handset battery slide open the plastic panel on the back of the Handset f To change the Receiver Batteries remove the Ash Pan Cover and locate the electronic receiver box u...

Страница 8: ...ss panel d The outer surfaces of the fire can be cleaned with a damp cloth do not use any abrasive cleaners For Stainless Steel finishes we recommend a small amount of Baby Oil IMPORTANT The Fire Must...

Страница 9: ...efficient fire may be more suitable or flue lining may need considering d Take account of the fire previously fitted and if the heat output will be sufficient for the room size and heat requirements...

Страница 10: ...ALLATION READ THESE INSTRUCTIONS CAREFULLY THESE INSTRUCTIONS SHOULD BE LEFT WITH THE USER FOR SAFE KEEPING AND FUTURE SERVICING PRIOR TO INSTALLATION ENSURE THAT THE GAS TYPE AND PRESSURE ARE AS STAT...

Страница 11: ...Test see Section 18 2 b For other Countries refer to National Regulations and Local Codes c This appliance is fitted with an oxygen depletion sensing system which automatically shuts off the gas suppl...

Страница 12: ...lace opening Sections 11 13 are for the various Installation Applications Only one will apply IMPORTANT NOTE The chosen installation should have been predetermined and arranged before installing the f...

Страница 13: ...t which is sensitive to dampness and high humidity so it is very important that any rendering building work is allowed to thoroughly dry out before Installation IMPORTANT NOTE Dry lined walls ensure t...

Страница 14: ...FLUE Fire Surround Requirements Pre Cast Flue Application With Fire Surround or Equivalent Pre Cast Fireplaces Minimum Requirements 65 Min Fire Surround Back Panel 630 min 470 max 300 min 630 min 65mi...

Страница 15: ...seal between the face of the surround and the sealing flanges of the fire l The Fireplace Opening should have provision for a gas supply through the rear see Section 10 Gas Supply m The Thermatronic...

Страница 16: ...ip must extend up to the underside of the shelf a A suitable BS715 Shallow Flue Box should be used with the minimum dimensions quoted above b The base of the Flue Box must be level and square to the f...

Страница 17: ...ensitive to dampness and high humidity so it is very important that any rendering building work is allowed to thoroughly dry out before Installation IMPORTANT NOTE Do not forget to take account of the...

Страница 18: ...at the Bottom Left and Right corners Securing the Glass Frame and ease it outward slightly at the base then pull down and remove IMPORTANT NOTE TAKE GREAT CARE WHEN WORKING INSIDE THE FIRE NOT TO MAR...

Страница 19: ...nd Lock Screw can now be fitted through the hole in the Back Box onto the cable and tightened up to tension the fire back into the fireplace The fire should be secure and not liable to movement Surplu...

Страница 20: ...he Front Moulded Coal into positions between Front Heat Shield and Burner as shown Health Safety Advice Refractory Ceramic Fibre RCF Advice when working with Fuel Bed Components including Installing S...

Страница 21: ...a flat side up against the back and the other down on to the Rear Coal Then place the others either side leaning against the centre Coal as shown d Take 2off J coals and place either side of coals jus...

Страница 22: ...Front LH RH corners as shown h Fit 3off J Coals along the front on top of those fitted earlier as shown h Fit 2off small G Coals along the front one either side of those just fitted as shown h Finally...

Страница 23: ...ion of the glass and also ensure it is clean and free from any finger marks Note The glass is etched with the Nu Flame logo and the glass is to be positioned with the logo in the bottom right hand cor...

Страница 24: ...fitted as shown Ensure the lug extended under the Wood Piece is located into the Cavity in the Front Wood Piece e Fit No 3 Wood Piece in the Centre as shown f Fit No4 Wood Piece to the right of the wo...

Страница 25: ...he 2 screws and screw driver provided check the condition of the glass and also ensure it is clean and free from any finger marks Note The glass is etched with the Nu Flame logo and the glass is to be...

Страница 26: ...ove The majority of the smoke must be drawn into the duct Some small whiffs of smoke may be expelled and this is quite normal Be careful not to introduce too much smoke i e by using a pellet A smoke m...

Страница 27: ...peration of the fire 18 1 GENERAL Note Servicing must be carried out by a registered installer a The fire does not have to be removed for Servicing however you will need to remove the Case as detailed...

Страница 28: ...ime and or gas control Refer to Section 22 for Cable connections diagram 19 3 PILOT GOES OUT AFTER FIRST LIGHTING a Check there is no debris blocking the flame to the thermocouple b Check the thermoco...

Страница 29: ...eographical location and so if a Flue Problem is thought likely but no problem is found during the investigation isolate the fire and seek expert advice 19 8 THERMATRONIC RADIO FREQUENCY CONTROL SYSTE...

Страница 30: ...e must be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited Mode...

Страница 31: ...st be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited Model Fe...

Страница 32: ...ect of the declaration described above is in conformity with relevant harmonized legislation Gas Appliance Regulation EU 2016 426 The following harmonised standards and technical specification have be...

Страница 33: ...33 22 DIAGRAM OF RADIO FREQUENCY CONTROL SYSTEM...

Страница 34: ...rn delivery to us We will not be liable for any such breakages Under no circumstances should any attempt be made to repair the burner on site without our express knowledge and approval during the warr...

Отзывы: