Table 2-2 Minimum and Maximum Modulation Rates 

Model 

Min. Modulation Rate (RPM) 

Max. Modulation Rate (RPM) 

Input Rate (MBH) 

Min 

Max 

1

 

FTG 2000 

1050 

7100 

235 

2000 

FTG 2200 

1050 

7200 

235 

2200 

FTG 2400 

1050 

8000 

235 

2350 

Notes: 

1

 

Canada: Altitudes between 2000-4500 ft, de-rate by 10%. Consult local authorities for de-rating for altitudes above 4500ft. 

2

 

Use 

Diagnostic Test

, accessed from the 

Diagnostic 

menu of the display, to force max. and min. modulation rates; see 

Appendix A – Controller and Touchscreen Display Instructions, Section 5 DIAGNOSTICS PAGE. 

 

 

Figure 2-1  Gas Valve Offset Check/Adjustment 

 

 

 

Differential Pressure 
Manometer 

– 

min. graduation 

of 0.01 in. w.c (1 Pa)

 

Offset Adjustment Procedure: 

1)  Differential Pressure Manometer

 

– obtain a 

meter capable of measuring differential 
pressure (“+” and “-“ ports) with a minimum 
graduation of 0.01 inches w.c. (or 1 Pa).

 

2)  Installation

 

– with the burner off, remove the 

caps from the pressure tappings.  Connect 
the Feedback Pressure Tapping to the 
Positive (+) port of the manometer; connect 
the Manifold Pressure Tapping to the 
Negative (-) port of the manometer.   Verify 
that the manometer is reading zero 

– zero the 

meter if necessary.

 

3)  Calibrate Combustion

 

– operate burner to 

maximum modulation rate (see Table 2-2), 
ensuring gas line pressure is maintained 
above 4 inches w.c.; set combustion 
according to Table 2-1 using the Throttle 
Screw 

– record CO

2

 value.

 

4)  Set Offset

 

– operate burner to minimum 

modulation rate (see Table 2-2); set offset 
pressure according to Table 2-1 using the 
Offset Screw.

 

NOTICE

Since the Manifold Pressure Tapping 

is connected to the Negative (-) port of the 
manometer, a negative Offset Pressure will 
read positive; e.g., to achieve an offset 
pressure of -0.03, manometer will read +0.03. 

5)  Verify Combustion

 

– with the burner 

remaining in operation at the minimum 
modulation rate, measure combustion and 
compare to readings obtained during 
maximum modulation 

– CO

2

 must be 0.5 to 

1.0% lower at minimum modulation.  If 
readings are out of tolerance 

– CONTACT 

NTI FOR ASSISTANCE.

 

6)  Complete Test 

– shutdown the burner, 

remove the manometer tubing and reinstall 
the factory caps on Offset Pressure Tappings. 

 

Positive (+)

 

Negative (-)

 

Feedback 

Pressure

 

Manifold 

Pressure

 

Throttle Screw

 

Used to calibrate combustion at max. 
modulation rate (use slot screw driver)

 

Offset Screw 

– used to set offset and 

combustion at min. modulation rate.   
Follow directions on screw 

– minus reduces 

offset/CO

2

 (use 2.5 mm

 

hex wrench)

 