2.0 Gas Valve and Burner Setup
Failure to perform the Gas Valve and Burner Setup correctly may result in incorrect
operation, component failure, property damage, serious injury or death.
Operating Sequence
Prior to commencing the Gas Valve and Burner Setup, perform the following operating sequence check:
1.
Turn the supply of gas to the boiler off.
2.
Set the thermostat to the highest setting.
3.
Ensure the combustion fan pre-purges for at least 30 seconds prior to activating the igniter.
4.
Ensure the combustion fan post-purges for at least 60 seconds prior to reactivating the igniter.
5.
Set the thermostat to the lowest setting and continue with the Gas Valve and Burner Setup procedure outlined
below.
Combustion Calibration Procedure
To calibrate burner combustion, perform the following procedure using a calibrated combustion analyzer capable of
measuring CO
2
and CO from a Natural Gas or Propane burning appliance:
1.
Set analyzer
to the appropriate fuel (Propane).
2.
Gas Line Pressure Test
– monitor gas line pressure throughout all combustion tests and verify it is maintained
within tolerance. See
Gas Line Pressure Test
below.
3.
Set Throttle Screw
– operate burner to the maximum modulation rate (see Table 2-2); set combustion according
to Table 2-1 using the Throttle Screw; allow time for the analyzer readings to stabilize between adjustments –
record CO
2
value. See
Throttle Screw Adjustment
below.
4.
Set Offset Screw
– operate burner to the minimum modulation rate (see Table 2-2); using the Offset Screw, set
the CO
2
to 0.5-1.0% lower than the value obtained during the maximum modulation rate test (e.g. if CO
2
at Max
= 10%, then CO
2
at Min must = 9.0-9.5%). Perform the Gas Valve Offset Check/Adjustment procedure detailed
in Figure 2-1. See
Offset Screw Adjustment
below.
Combustion Calibration is mandatory
upon installation and during each annual service.
Failure to perform the Combustion Calibration in accordance with these instructions may
result in incorrect combustion leading to burner damage or excessive Carbon Monoxide
concentrations causing property damage, personal injury or death.
Carbon Monoxide
- Never leave the unit operating while producing Carbon Monoxide (CO)
concentrations in excess of 175 ppm. Failure to follow this warning may result in serious
injury or death.
Throttle Screw Adjustment
The gas valve Throttle Screw (see Figures 1-1) is used to calibrate the CO
2
concentration with the burner operating at
or near the maximum modulation rate (see Table 2-2). Turning the Throttle Screw in (clockwise) decreases the CO
2
concentration. Turning the Throttle Screw out (counterclockwise) increases the CO
2
concentration.
Typical
adjustment required is 0 -
1
/
8
th
of a turn in or out from the position established in Section 1.0 above.
NOTE:
Calibration of the Throttle Screw should only be performed with the burner operating at or near the
maximum modulation rate (see Table 2-2).
Adjustments to the
Throttle Screw
may only be made by a qualified gas technician using a
calibrated combustion analyzer capable of measuring CO
2
and CO. Adjustments may only be
performed if the gas line pressure is maintained above minimum levels throughout the
duration of the test (see Table 2-1). Failure to follow these instructions may result in serious
injury or death.