NTI FTG 2000 Скачать руководство пользователя страница 4

  

Offset Screw Adjustment 

The gas valve Offset Screw (see Figures 1-1 & 2-1) is used to calibrate the CO

2

 offset at minimum modulation vs. 

maximum modulation.  Making the offset more positive (+) increases the CO

concentration at minimum modulation 

rate; making the offset more negative (-) decreases the CO

concentration at minimum modulation rate.

  

 

 NOTE: 

  

Calibration  of  the  Offset  Screw  must  only  be  performed  with  the  burner  operating  at  the  minimum 
modulation rate (see Table 2-2). 

 

Adjustments  to  the 

Offset  Screw

  may  only  be  made  by  a  qualified  gas  technician  using  a 

calibrated combustion analyzer capable of measuring CO

2

 and CO, and only with the burner 

at the minimum modulation rate (see Table 2-2).  Attempting to set the Offset Screw while the 
burner  is  operating  at  a  modulation  rate  other  than  the  minimum  will  result  in  incorrect 
combustion and may lead to burner damage or excessive CO. 

 

Gas Line Pressure 

The  boiler  gas  valve  is  equipped  with  a  line  pressure  test  port;  see  Figure  1-1.  Use  the  following  procedure  to 
measure the gas line pressure to the boiler to ensure if falls within the range given in Table 2-1: 

 

1.

 

Turn the supply of gas to the boiler off. 

2.

 

A  bleed  screw  is  located  on  the  inlet  flange  of  the  gas  valve;  open  it  approximately  1-1/2  turns.    See 

Line 

Pressure Test Port

 in Figure 1-1. 

3.

 

Slide the gas pressure manometer tubing over the bleed screw fitting located on the inlet flange of the gas valve; 

connect the other end of the tubing to the gas pressure manometer.  Ensure both ends of the tubing make a tight 
connection. 

4.

 

Open the supply of gas to the boiler and check for gas leaks. 

5.

 

Observe the line pressure under static conditions and compare it to Table 2-1. The pressure will be greatest under 

static conditions. 

6.

 

With all other gas appliances in the application running, operate the burner to the maximum firing rate (see Table 

2-2) and compare the observed line pressure with Table  2-1. The pressure will be lowest during the maximum 
flow of gas. 

7.

 

Adjust the gas line pressure to ensure the parameters in Table 2-1 are attained under all conditions (see NOTICE 

below).  If possible, adjust the line pressure to the "Nominal/Desired" value listed in Table 2-1, while the unit is 
operating at the maximum modulation rate, see Table 2-2. 

8.

 

Continue  observing  the  gas  line  pressure until  the  completion of the  combustion  analyses, in case  adjustments 

need to be made. 

9.

 

Upon completion of the line pressure testing, turn the gas supply off and close the bleed screw.  Turn gas on and 

check for leaks.  

 

The  line  pressure  is  a  function  of  the  gas  supply  and  is  affected  solely  by  field  provided 
parameters such as line size and regulator settings.  Under no circumstances can the boiler gas 
valve influence or be used to adjust the gas line pressure. 

 

Failure to properly close the 

Line Pressure Test Port

 bleed screw will cause severe leakage 

of gas, resulting in a fire or explosion causing property damage, serious injury or death.     

 

Table 2-1 Line Pressure and Combustion Parameters

 

 

Gas 

Line Pressure (inches w.c.) 

Offset Pressure 

(inches w.c. / [Pa])

 2 

CO

2

 (%)

 1 

Max. CO 

(ppm) 

Nominal/

Desired 

Min. 

Max. 

Min. 

Max. 

Natural 

10.5 

-0.01 to 0 / [-3 to -1] 

8.3 

9.3 

175 

Propane 

11 

13 

-0.04 to -0.03 / [-10 to -8] 

9.6 

10.6 

175 

Notes: 

1

 

Combustion values listed are for burner operation at maximum modulation rate; when tested at minimum modulation 
rate the CO

2

 must be 0.5-1.0% lower than CO

2

 at maximum modulation rate. 

2

 

The Offset Pressure must be checked, and if necessary adjusted, in accordance with the procedure detailed in Figure 2-1.  

 
 
 
 
 

Отзывы: