E1400 Installation Guide
preliminary
6.13
X20
X20
Analog In (+-10V Differential Analog Input)
1
2
3
4
5
6
7
8
case
Do not connect
Do not connect
Analog In -
GND
GND
Analog In +
Do not connect
Do not connect
Shield
RJ-45
6.14
X29
X29
Connector for Fan Option
Spring cage terminal block for connecting the external fan option (Art. Nr. 0150-xxxx).
Output: 24 VDC / 0.4 A (Short circuit protected, current monitored)
Stripping length: 8mm
Conductor cross section: 0.2 – 1.5 mm
2
(AWG 24 - 16)
6.15
S5
S5
Bus Termination / AnaIn2 Pull Down
S5
Switch 6: Override Configuration Ethernet to DHCP
Switch 5: Bootstrap: Must be off for normal operation
Switch 4: CAN termination on ME (120R between pin 7 and 8 on X10/X11) on/off
Switch 3: CAN termination on CMD (120R between pin 7 and 8 on X7/X8) on/off
Switch 2: Termination resistor for RS485 on CMD (120R between pin 1 and 2 on X7/X8) on/off
Switch 1: AnIn2 pull down (4k7 Pull down on X4.4). Set to ON, if X4.4 is used as digital output.
Factory setting: all switches “on” except S5.5 (Bootstrap) and S5.6 (Override to DHCP)