7.0 REVIEW, MODIFY, AND DELETE
Press
MODE
to advance to any of the following MODES:
1. AUTO MODE:
In this automatic mode, the unit will ex-
ecute the scheduled programs. Time, day, seconds and
load status are displayed. If today is a programmed
holiday, the day of the week will flash.
OVERRIDE IN AUTO MODE:
The load status of the chan-
nel can be manually changed by pressing the
OVRD
key (or
OVR1
and
OVR2
key for DG200A).
The unit will stay in this position until the next sched-
uled event. A flashing LCD load indication (ON, OFF)
shows the status was changed by the override not a
scheduled event.
2. MAN MODE:
In this manual mode, the unit will ignore
the schedule programs. Time, day, seconds and load
status are displayed. If today is a programmed holiday,
the day of the week will flash. This can be used as a
VACATION SETTING to keep load off while away. Use
override to set to OFF position.
OVERRIDE IN MAN MODE:
The load status of the chan-
nel can be manually changed by pressing the
OVRD
key (or
OVR1
and
OVR2
key for DG200A).
The unit will stay in this position until
OVRD
is pressed
again. A flashing LCD load indication (ON, OFF)
shows the status was changed by the override not a
scheduled event.
3. CLOCK MODE:
Press
HOUR
and
MIN
to modify existing
settings. Press
ENTER
to save changes.
4. DATE MODE:
Press
MONTH
,
DATE
, and
YEAR
to modify
existing settings. Press
ENTER
to save changes. DAY is
automatically adjusted.
NOTE:
Selection #12 will only show if a holiday date has
been entered in Step 5.
Press
ENTER
to save.
Follow the same procedures above to set more schedule
entries.
Press
MODE
when schedules are complete.
Unit is in the AUTO (automatic) mode.
The word FLASH may appear to indicate a new program
has been written to memory.
Press the
EVENT
key once (or twice for two circuit units)
to activate the current schedule then press the
EVENT
key
again to return to AUTO mode.