Timer NT240
NOVUS AUTOMATION
5/5
Mode 8 – Pulse after a continuous START signal
Start
t1.SP
Out 1
Reset
t1.SP
t1.SP
T1.S1
to
T1.S5
are automatically set to:
T1.S1
T1.S2
T1.S3
T1.S4
T1.S5
1
2
2
0
0
•
The
F
key can only be used for holding the temporization in
progress.
Mode 9 – Delayed output after a continuous START signal
Start
t1.SP
Out 1
Reset
t1.SP
t1.SP
T1.S1
to
T1.S5
are automatically set to:
T1.S1
T1.S2
T1.S3
T1.S4
T1.S5
1
2
3
2
0
•
The
F
key can only be used for holding the temporization in
progress.
Mode 10 – Delayed pulse after continuous START signal
Start
t1.SP
Out 1
t1.SP
Reset
ou1.t
t1.SP
T1.S1
to
T1.S5
are automatically set to:
T1.S1
T1.S2
T1.S3
T1.S4
T1.S5
1
2
3
1
0
•
The
F
key can only be used for holding the temporization in
progress.
Mode 11 – Customized Mode of Operation
In this mode, the operator is allowed to create his own mode of
operation if the predefined ones don’t meet the process needs. This
can be accomplished through parameters
t1.S1
to
t1.S5
in the
Custom Operating Mode level of parameters. The user must analyze
each one of the 5 parameters and understand the effect that each
one has on the timer. The user must consider that not all the
combinations of the parameters
t1.S1
to
t1.S5
are valid, and that
some combinations may lead to unexpected behaviors.
When programming a customized operation mode, the user must test
it to verify that it suits the application before incorporating it to the
system.